Plan Review Notes
Plan Review Notes For Permit 22071171
Permit Number 22071171
Review Stop B
Sequence Number 3
Notes
Date Text
2022-12-12 10:35:17REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE GUARD RAIL HEIGHT ALONG THE STAIRWAY
 - FBC 1015.3 HEIGHT.
 REQUIRED GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067
 MM) HIGH,
  
 FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 2) PLEASE SHOW THE HANDRAIL EXTENSIONS - FBC
 1014.6HANDRAIL EXTENSIONS.
 THE HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN
 12 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
  
  
  
  