| Plan Review Notes For Permit 22071171 |
| Permit Number |
22071171 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-12-21 05:57:11 | 2ND REVIEW FMC | | | PERMIT: 22071171 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DESIGNER OF RECORD FOR THE ORIGINAL DESIGN MUST | | | SUBMIT THE REVISED DRAWINGS OR SUBMIT A LETTER STATING | | | THEY ARE RELEASING THEMSELVES FROM THIS PROJECT. | | | | | | 2) THE MECHANICAL DRAWING SUBMITTED DOES NOT INDICATE | | | WHICH FLOOR THIS NEW SPACE WILL BE LOCATED IN THIS | | | BUILDING. PROVIDE A FULL SET OF DRAWINGS FOR THIS | | | REVISION. FBC 107.3.5 | | | | | | 3) PROVIDE THE COMPLETE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC C403.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|