Plan Review Notes
Plan Review Notes For Permit 22071171
Permit Number 22071171
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-17 11:08:56REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) BUILDING CONSTRUCTION TYPE SHOWN "TYPE II" - DOES
 NOT ALLOW COMBUSTIBLE CONSTRUCTION - I THINK THAT THE
 CONSTRUCTION TYPE COULD BE TYPE III B - SEE FBC TABLE
 506.2
  
 2) OCCUPANT LOAD - DRAWINGS SHOW "50 GROSS" - PLEASE
 SHOW THE OCCUPANT LOAD FOR THE TRAINING AREA - FBC 1004
 PLEASE SEE TABLE 1004.5 AND SHOW THE "FUNCTION OF THE
 SPACE" AND THE OCCUPANT LOAD CORRECTLY.
  
 3) STAIR AND BALCONY GUARD RAIL OPENINGS FOR THE
 TRAINING AREA NEED TO COMPLY WITH FBC 1015.4 OPENING
 LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 4) PLEASE SHOW THE GUARD RAIL HEIGHT ALONG THE STAIRWAY
 - FBC 1015.3 HEIGHT.
 REQUIRED GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067
 MM) HIGH,
  
 5) SHOW THE VERTICAL ACCESSIBILITY TO THE 2ND FLOOR PER
 FBC 201.1.1
  
 6) PLEASE SHOW THE SQUARE FOOTAGE OF THE 2ND FLOOR FBC
 1004.5
  
 7) PLEASE SHOW IF THE BUILDING HAS FIRE SPRINKLERS OR
 NON SPRINKLERED.