| Plan Review Notes For Permit 22071171 |
| Permit Number |
22071171 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-10-17 11:08:56 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) BUILDING CONSTRUCTION TYPE SHOWN "TYPE II" - DOES | | | NOT ALLOW COMBUSTIBLE CONSTRUCTION - I THINK THAT THE | | | CONSTRUCTION TYPE COULD BE TYPE III B - SEE FBC TABLE | | | 506.2 | | | | | | 2) OCCUPANT LOAD - DRAWINGS SHOW "50 GROSS" - PLEASE | | | SHOW THE OCCUPANT LOAD FOR THE TRAINING AREA - FBC 1004 | | | PLEASE SEE TABLE 1004.5 AND SHOW THE "FUNCTION OF THE | | | SPACE" AND THE OCCUPANT LOAD CORRECTLY. | | | | | | 3) STAIR AND BALCONY GUARD RAIL OPENINGS FOR THE | | | TRAINING AREA NEED TO COMPLY WITH FBC 1015.4 OPENING | | | LIMITATIONS. | | | REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW | | | PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM | | | THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. | | | | | | 4) PLEASE SHOW THE GUARD RAIL HEIGHT ALONG THE STAIRWAY | | | - FBC 1015.3 HEIGHT. | | | REQUIRED GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067 | | | MM) HIGH, | | | | | | 5) SHOW THE VERTICAL ACCESSIBILITY TO THE 2ND FLOOR PER | | | FBC 201.1.1 | | | | | | 6) PLEASE SHOW THE SQUARE FOOTAGE OF THE 2ND FLOOR FBC | | | 1004.5 | | | | | | 7) PLEASE SHOW IF THE BUILDING HAS FIRE SPRINKLERS OR | | | NON SPRINKLERED. |
|