| 2022-10-04 08:59:09 | 1ST REVIEW FMC | | | PERMIT: 22071171 | | | | | | CODES IN EFFECT: 2020 | | | | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A COMPLETE SCOPE OF WORK FOR THE MECHANICAL | | | DESIGN. FBC 107.3.5 | | | | | | 2) THERE IS A 1 PAGE MECHANICAL SIZING SHEET SUBMITTED, | | | THE DUCTWORK DRAWING DOES NOT SHOW A NEW SYSTEM. PLEASE | | | EXPLAIN WHAT THIS SHEET IS SERVING. | | | | | | 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS NEW | | | TRAINING AREA. FMC 403.3.1.1 | | | | | | 4) THE DRAWING SUBMITTED IS NOT FROM THE EOR FOR THIS | | | PROJECT PLEASE SUBMIT A DRAWING FROM THIS DESIGNER OR A | | | CHANGE OR EOR. 61G15-27.001 | | | | | | 5) THE DRAWING SUBMITTED DOES NOT SHOW THE MAIN TRUNK | | | LINE SIZES, PLEASE SHOW THE MAIN TRUNK LINE SIZES. FBC | | | 107.3.5 | | | | | | 6) THE REVISION APPLICATION SUBMITTED DOES NOT SHOW A | | | VALUE FOR THIS NEW SCOPE OF WORK. PROVIDE A VALUE FOR | | | THIS REVISION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|