| Plan Review Notes For Permit 22071150 |
| Permit Number |
22071150 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-23 17:01:04 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-22071150 | | | 9/23/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-501: PROVIDE PLUMBING RISER DRAWINGS- SEC. | | | 107.3.5.1.3 WPB. | | | | | | 2) P-501: PROVIDE A MEANS OF DELIVERING THE REQUIRED | | | HOT WATER FROM THE LOUNGE SINK, AND A MEANS OF LIMITING | | | THE TEMPERATURE OF THE HOT WATER- REFER TO SECS. 607.1 | | | & 607.1.1 FBC P. | | | | | | 3) P-001; PROVIDE A PLUMBING FIXTURE AND EQUIPMENT | | | SCHEDULE ON THE- SEC. 107.3.5.1.3 WPB. | | | | | | 4) P-501: THE PLAN SHOWS THE NEW SANITARY PIPING RUN IN | | | THE CEILING BELOW THE FLOOR. PLEASE CLARIFY IF THE | | | SPACE IS A PLENUM AND INDICATE THE TYPE OF DWV AND | | | WATER PIPING WILL BE INSTALLED- SEC. 303.2 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|