| Plan Review Notes For Permit 22071150 |
| Permit Number |
22071150 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-16 15:07:37 | 1ST REVIEW FMC | | | PERMIT: 22071150 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF | | | THE TENANT SPACE. FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 2) THE EXHAUST FROM THE PRINTING ROOM MUST BE EXHAUSTED | | | TO THE OUTDOORS AND NOT INTO THE RETURN AIR PLENUM. FMC | | | TABLE 403.3.1.1 | | | | | | 3) PROVIDE THE DUCT SIZES FOR THE SUPPLY DUCT FOR | | | VAV-10-RH-3. FBC 107.3.5 | | | | | | 4) SHEET M-401: IDENTIFY EACH VAV IN THE TERMINAL BOX | | | SCHEDULE TO MATCH SHEET M-501. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|