| 2022-11-21 14:34:51 | N/A |
| | |
| 2022-09-27 15:53:42 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22071147 250 S AUSTRALIAN AVE FL 11 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE A NOTE ON PLAN SHEETS |
| | P-001, A101 AND A401 "REFER TO PLAN SHEETS G007, G008, |
| | G009, G010, G011 AND G012 FOR ALL ACCESSIBILITY |
| | REQUIREMENTS. IN CASE OF DISCREPENCY G007, G008, G009, |
| | G010, G011 AND G012 REQUIREMENTS SHALL PREVAIL." FBC |
| | ACC CHAPTERS 3 AND 6. |
| | |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE WATER HEATER |
| | ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| | 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| | ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. PROVIDE A |
| | NOTE ON P-001 LISTING ANY DEFERRED SUBMITTALS. |
| | |
| | 3. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN SHEET P-101 |
| | STATING THE SAME. |
| | |
| | 4. PLAN SHEET P-101/PLUMBING SPECIFICATIONS: PER WPB |
| | FBC 107.2.1, MAKE THE FOLLOWING CORRECTIONS. |
| | ***A) NOTE 1-A; REPLACE "2017" WITH "2020" |
| | ***B) NOTE 8-F (3); SOLDER SHALL BE LEAD FREE, NOT |
| | TIN/ANTIMONY. FBC PL 605.2 AND 605.2.1 |
| | ***C) NOTE 21-A; REPLACE "R" WITH "1/4 ". FBC PL 704.1 |
| | |
| | |
| | 5. P-501/PLUMBING HEX NOTE EWH-1 AND EWH-2: PER WPB FBC |
| | 107.2.1, PLEASE PROVIDE THE FOLLOWING; |
| | ***A) NOTE COMPLIANCE WITH ASSE 1070; IF IT DOES NOT |
| | COMPLY WITH ASSE 1070 THEN A THERMOSTATIC MIXING VALVE |
| | FOR THE LAVATORIES COMPLYING WITH ASSE 1070 SHALL BE |
| | PROVIDED PER FBC PL 419.5. |
| | ***B) PROVIDE A DEDICATED VALVE IN THE COLD WATER |
| | SUPPLY TO THE WATER HEATER PER FBC PL 503.1 |
| | |
| | 6. PER WPB FBC 107.2.1, 107.3.5.1.3 (3), FBC PL 601 AND |
| | 604.3, PROVIDE CALCULATIONS FOR SIZING OF THE WATER |
| | DISTRIBUTION SYSTEM. METHOD PROVIDED AS NOTED IN FBC PL |
| | APPENDIX E, SECTION 103 IS AN APPROVED METHOD FOR |
| | DETERMINING PIPE SIZE. |
| | |
| | 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3 (3), FBC PL 601 |
| | AND 604.3, PROVIDE ON THE WATER RISER DIAGRAM SIZING OF |
| | ALL SEGMENTS OF THE WATER DISTRIBUTION SYSTEM. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | |