| 2022-09-06 13:43:46 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22071084 |
| | ADD: 3800 WASHINGTON RD # 211 |
| | CONT: PROJECT SOLUTIONS LLC |
| | TEL: |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 09/2022 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE VALUE OF THE |
| | PROJECT TO BE $106,000.00 DOLLARS. THE EXISTING AND |
| | PROPOSED FLOOR PLAN ARE DRAWN BY THE CGC PLEASE REVIEW |
| | W 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION AND FLORIDA |
| | STATUTE 481. CERTIFICATION BY CONTRACTOR. 107.3.4.3. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS AND OR SCHEDULES WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS AND OR SCHEDULES |
| | DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE |
| | LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR |
| | THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C) |
| | ANY OTHER TYPE OF BUILDING COSTING LESS THAN |
| | $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER |
| | BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE |
| | SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE |
| | REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45. |
| | 2) SCOPE OF WORK INDICATES THE REMOVAL OF ALL FLOOR |
| | TILE AND INSTALLATION OF NEW FLOOR TILE. FLOOR |
| | INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, |
| | MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD |
| | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO |
| | DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE |
| | & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 3) NEW THROUGH FLOOR PENETRATIONS. THROUGH-PENETRATIONS |
| | FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW |
| | FLOOR PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN, |
| | THEN YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B |
| | SECTION 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP |
| | SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS |
| | SHALL BE PROTECTED BY A THROUGH PENETRATION FIRESTOP |
| | SYSTEM INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL |
| | 1479. THE SYSTEM SHALL HAVE AN F RATING / T RATING OF |
| | NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED |
| | RATING OF THE FLOOR PENETRATED. |
| | |
| | 4) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A |
| | BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR |
| | SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING |
| | BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT |
| | WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM |
| | C840 AND THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 5) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |