2022-08-24 10:42:13THE CURRENT USE OF THIS BUILDING IS BUSINESS AND THE
 OCCUPANT IS A BANK. THE PROPOSED USE IS MERCANTILE
 WHICH IS A CHANGE OF OCCUPANCY THE APPLICATION SHOULD
 REFLECT THIS CHANGE OF USE. THE MECHANICAL SYSTEM MUST
 MEET THE MERCANTILE REQUIREMENTS OF FMC 403.3.1.1 AND
 TABLE 403.3.1.1 FOR THE OUTDOOR AIR AS THE OCCUPANCE
 DENSITY PER 1000 SQ,FT. IS HIGHER IN THE MERCANTILE
 OCCUPANCY. PROVIDE THE MECHANICAL SCOPE OF WORK ALONG
 WITH DRAWINGS AND THE OUTDOOR AIR CALCULATIONS FOR THIS
 CHANGE OF USE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  