| Plan Review Notes For Permit 22071063 |
| Permit Number |
22071063 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-24 10:42:13 | THE CURRENT USE OF THIS BUILDING IS BUSINESS AND THE | | | OCCUPANT IS A BANK. THE PROPOSED USE IS MERCANTILE | | | WHICH IS A CHANGE OF OCCUPANCY THE APPLICATION SHOULD | | | REFLECT THIS CHANGE OF USE. THE MECHANICAL SYSTEM MUST | | | MEET THE MERCANTILE REQUIREMENTS OF FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 FOR THE OUTDOOR AIR AS THE OCCUPANCE | | | DENSITY PER 1000 SQ,FT. IS HIGHER IN THE MERCANTILE | | | OCCUPANCY. PROVIDE THE MECHANICAL SCOPE OF WORK ALONG | | | WITH DRAWINGS AND THE OUTDOOR AIR CALCULATIONS FOR THIS | | | CHANGE OF USE. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|