Plan Review Notes
Plan Review Notes For Permit 22071043
Permit Number 22071043
Review Stop B
Sequence Number 2
Notes
Date Text
2022-09-20 10:02:46PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE COMMENTS FROM THE PREVIOUS REVIEW WERE NOT
 RESOLVED.
  
 1) THE SOUND TESTING REPORTS THAT YOU SUBMITTED ARE FOR
 A 6" SLAB WITH A SUSPENDED CEILING BELOW IT. THIS
 BUILDING DOES NOT HAVE A SUSPENDED CEILING BELOW THE
 FLOOR. THE TEST HAS TO MATCH THE CONDITIONS AT THE
 SITE. SUBMIT THE FOLLOWING TEST REPORTS FOR THE SOUND
 UNDERLAYMENT: E-90 & E-492.
  
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 SUBMIT THE TEST REPORTS FOR THE SOUND INSULATION WHERE
 THERE IS NO CEILING ASSEMBLY BELOW THE FLOOR SLAB.
  
  
  