| Date |
Text |
| 2022-09-06 15:27:07 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE SOUND TESTING REPORTS THAT YOU SUBMITTED ARE FOR |
| | A 6" SLABE WITH A SUSPENDED CEILING BELOW IT. THIS |
| | BUILDING DOES NOT HAVE A SUSPENDED CEILING BELOW THE |
| | FLOOR. THE TEST HAS TO MATCH THE CONDITIONS AT THE |
| | SITE. SUBMIT THE FOLLOWING TEST REPORTS FOR THE SOUND |
| | UNDERLAYMENT: E-84, E-90 & E-492. |
| | - FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| | |
| | - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | SUBMIT THE TEST REPORTS FOR THE SOUND INSULATION |
| | INCLUDING FLAME SPREAD AND SMOKE DEVELOPED FOR THE |
| | APPLICABLE CONSTRUCTION CONDITIONS. |
| | |
| | |
| | |