| Plan Review Notes For Permit 22071014 |
| Permit Number |
22071014 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-22 11:58:39 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1. FBC B 107.2.1 PLEASE CLARIFY; PAGES #51 & 52 SYSTEM | | | E (1) OF MAIM-DADE NOA NO. 18-0919.12 WAS SUBMITTED; IF | | | USING THIS SYSTEM REVISE ENGINEERS CALCULATIONS TO | | | REFLECT THIS SYSTEM; ALTERNATIVELY PROVIDE THE | | | FOLLOWING INFORMATION FOR MIAMI-DADE COUNTY NOA NO.: | | | 18-0919.12 THE PROPOSED FLAT ROOF SYSTEM TO BE USED | | | CORRESPONDING TO THE SUBMITTED ENGINEERS CALCULATIONS; | | | INSTALLATION INSTRUCTIONS FOR SYSTEM USED A(1) PAGES | | | #9 - 11. | | | 2. SUBMITTED MIAMI-DADE COUNTY NOA 20-0723.36 COVERS | | | MULTIPLE APPROVED ASSEMBLIES: SYSTEMS E(1) THROUGH | | | E(5). SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS | | | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE | | | PRODUCT APPROVAL DRAWINGS. |
|