| 2022-08-10 14:38:22 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22070933 |
| | 8/10/2022 |
| | |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: THE PRINTED NAME, SIGNATURE, LICENSE |
| | NUMBER OF THE CONTRACTOR OR QUALIFIER SHALL BE ON THE |
| | DRAWING- SEC. 107.2.1 WPB, AND FL. STATUTES |
| | 471.003(2)(H) & 471.025. |
| | |
| | 2) GAS RISER: SHOW THE TYPE AND SIZE OF THE PIPE FROM |
| | THE METER TO THE TEE, AND THEN FROM THE TEE ONWARD |
| | (DESTINATION NOT SHOWN). REFER TO SECS. G2412.3 & |
| | G2412.4 FBC RES. AND PROVIDE THE FOLLOWING INFORMATION |
| | ON THE DRAWING PER SECS. G2412.3 & G2412.4 FBC RES. |
| | A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | B) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | C) TYPES AND SIZES OF PIPING. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | F) OUTLET PRESSURES AT REGULATORS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |