| 2022-08-09 09:30:21 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. BATH NO. 2 - 2020 FRC P3108.1 - THE WATER CLOSET AND |
| | SHOWER ARE NOT VENTED CORRECTLY. THE WASHING MACHINE |
| | CANNOT BE INCLUDED IN THE WET VENT FOR BATHROOM GROUP |
| | FIXTURES. THE WASHING MACHINE WOULD NEED TO DISCHARGE |
| | DOWNSTREAM OF THE LAST BATHROOM GROUP FIXTURE. |
| | |
| | 2. REMODELED MASTER BATH - 2020 FRC P3108.2.1 - THE TUB |
| | AND SHOWER ARE NOT VENTED. ONLY ONE FIXTURE TRAP IS |
| | ALLOWED UPSTREAM OF THE VENTED FIXTURE'S CONNECTION. |
| | CURRENTLY, THERE ARE TWO TRAPS UPSTREAM. |
| | |
| | 3. REMODELED KITCHEN - YOU'VE MISLABELED THE KITCHEN |
| | SINK AND VEG. SINK AS LAVS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |