| Plan Review Notes For Permit 22070859 |
| Permit Number |
22070859 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-09 09:36:17 | 1ST REVIEW FMC | | | PERMIT: 22070859 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A MECHANICAL DRAWING THAT SHOWS ALL THE | | | DOORS ON THE DRAWING. FBC 107.2.1 | | | | | | 2) THE ENERGY CALCULATIONS SUBMITTED ARE LABELED FOR A | | | NEW ADDITION OF 1474 SQ. FT. PLEASE LABEL THIS ON THE | | | MECHANICAL DRAWING. FBC 107.2.1 | | | | | | 3) PROVIDE THE ANCHORAGE DETAILS FOR THE CONDENSING | | | UNITS. FRC M1307.2 | | | | | | 4) SHOW THE CONDENSATE PIPING AND TERMINATION | | | LOCATIONS. FRC M1411.3 | | | | | | 5) THE DESIGNER OF THE MECHANICAL DRAWING MUST SIGN | | | THEIR NAME ON THE DRAWING. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|