| Plan Review Notes For Permit 22070849 |
| Permit Number |
22070849 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-01 13:18:18 | ELECTRIC REVIEW FAILED | | | 1)PLEASE PROVIDE A FLOOR PLAN DETAILING ALL ELECTRICAL | | | WIRING TO BE REMOVED, MODIFIED OR ADDED. INCLUDE | | | ELECTRIC PANEL LOCATION. FBC 107.2 | | | 2) PLEASE PROVIDE ELECTRICAL SERVICE SPECIFICATIONS AND | | | LOAD CALCULATIONS IF ANY ADDITIONAL ELECTRIC LOADS ARE | | | TO BE ADDED. NEC 215.5 | | | 3) PLEASE DETAIL ON PLANS COMPLIANCE WITH ALL | | | APPLICABLE FLORIDA BUILDING AND NATIONAL ELECTRIC | | | CODES. FBC 107.2 | | | 4) PLEASE HAVE DESIGNER OF ALL PLANS SIGN THEM AS | | | REQUIRED. SECTION 107.2.1 WPB | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|