| 2022-07-28 12:53:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE ENGINEER REPORT UNDER PROJECT ASSUMPTION # 1, |
| | INDICATES THE BUILDING IS A SINGLE FAMILY HOME. |
| | |
| | MY RECORDS INDICATE THAT THIS IS A MULTI UNIT APARTMENT |
| | BUILDING. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE REVIEW TO ENSURE CORRECT IDENTIFICATION. |
| | |
| | |
| | 1A) THERE IS NO INDICATION OF IF THIS BUILDING AND |
| | MUTIPLE FAMILY RESIDENTS WILL BE ALLOWED TO REMAIN OR |
| | REQUIRED TO VACANT DURING THE CONSTRUCTION PROCESSING. |
| | |
| | IS THERE ANY DANGER OF COLLASPE OR WILL ANY EXITS BE |
| | BLOCKED BY THE CONSTRUCTION PROCESSES? |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND /OR A |
| | SITE PLAN AFFORDING PROTECTION OF THE RESIDENTS AND |
| | EXITING IN CASE OF EMERGENCY. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |