| 2022-09-06 14:28:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SURVEY SHOWS A FENCE, HOWEVER, I COULD NOT FIND | | | A FENCE PERMIT FOR THIS PROPERTY. IN ORDER FOR THE | | | FENCE TO BE UXED AS A POOL BARRIER IT IS REQUIRED TO BE | | | LOCATED ON THE PROJECT PROPERTY AND UNDER THE CONTROL | | | OF THE PROPERTY OWNER. | | | | | | 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | POOL ALARMS THAT ARE TO BE INSTALLED. FBC 107.2.1 | | | | | | 3) PROVIDE POOL EQUIPMENT ANCHORING DETAILS FOR WIND | | | LOADS OF 170 MPH VULT. SPECIFY THE NUMBER AND TYPE OF | | | ANCHORS FOR EACH TYPE OF EQUIPMENT. SPECIFY THE SIZE | | | AND EMBED DEPTH FOR THE ANCHORS. FBC-R301.2.1 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|