Date Text
2022-07-25 07:29:211) PROVIDE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT AND PROVIDE THE AMOUNT FOR THIS SYSTEM. FMC
 1102.1; 3
  
 2) IT APPERAS THAT THE REFRIGERATION UNIT IS LESS THAN
 4 FEET FROM THE ROOFS EDGE. SHOW THE REQUIRED GUARDS
 FOR THE SAFETY OF THE SERVICE TECH. FMC 304.11
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  