Plan Review Notes
Plan Review Notes For Permit 22070773
Permit Number 22070773
Review Stop P
Sequence Number 3
Notes
Date Text
2022-12-07 16:10:41ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO: PROVIDE CANE APRON FOR DRINKING FOUNTAIN. SEE
 A-601, DRINKING FOUNTAIN DETAIL, NOTE 6 AND FBC ACC
 307.2
  
 PROVISO: EEMAX EMT1.0 AND EEMAX EMT2.5 NOT SERVICING
 PUBLIC LAVATORIES SHALL BE PROVIDED WITH A TEMPERATURE
 ACTUATED MIXING VALVE CONFORMING TO ASSE 1017 PER FBC
 PL 607.1.1, 613.1
 THOSE SERVICING PUBLIC LAVATORIES SHALL BE PROVIDED
 WITH A WATER TEMPERATURE LIMITING DEVICE CONFORMING TO
 ASSE 1070 PER FBC PL FPC 419.5, 607.1.2
  
 PROVISO: THE REVERSE OSMOSIS SYSTEM IN THE KITCHEN
 SHALL BE PROVIDED WITH AN INDIRECT WASTE TO THE FLOOR
 SINK WITH AN AIR GAP. FPC 802.1.1
 THE WATER SUPPLY TO THE REVERSE OSMOSIS SYSTEM SHALL BE
 PROVIDED WITH A BACKFLOW PREVENTER. FPC 608.1
  