| 2022-10-10 16:51:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22070773 320 BELVEDERE RD |
| | |
| | |
| | 2ND REVIEW |
| | |
| | NOTE: A RESPONSE LETTER ADDRESSING EACH ITEM WAS NOT |
| | PROVIDED WITH THIS SUBMITTAL. |
| | |
| | PROVISO #1: P-2.01/KEYNOTES 20/21: A 3 INCH SANITARY |
| | DRAIN IS NOTED FOR THE DRY STORAGE ROOM; CONNECTION TO |
| | EXISTING SANITARY. A PLAN REVISION WILL BE REQUIRED |
| | SHOWING THE CONNECTION TO EXISTING. REVISION SHALL BE |
| | SUBMITTED, APPROVED AND IN PLACE AT TIME OF FINAL |
| | INSPECTION. DRAINS ARE REMOVED FROM DRY STORAGE PER |
| | ENGINEER; REVISION STILL REQUIRED TO SHOW NO DRAINS. |
| | SEE P-3.05. |
| | |
| | PROVISO #2: MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE FOLLOWING SHALL BE ON SITE PRIOR TO |
| | FINAL INSPECTION: |
| | ***A) WATER HEATER(S) |
| | ***B) BACKFLOW PREVENTER DEVICES |
| | ***C) THERMOSTATIC MIXING VALVES |
| | ***D) KITCHEN EQUIPMENT |
| | |
| | PROVISO #3: RMS 128/129 AND 130/131 ARE RECONFIGURED TO |
| | ELIMINATE ONE BATHROOM IN EACH CONFIGURATION; REMAINING |
| | BATHROOMS ARE RECONFIGURED. ROOM 127 BATHROOM IS |
| | RECONFIGURED. A PLAN REVISION WILL BE REQUIRED SHOWING |
| | THE REVISED WATER AND SANITARY. REVISION SHALL BE |
| | SUBMITTED, APPROVED AND IN PLACE AT TIME OF INSPECTION. |
| | |
| | PROVISO #4: P-2.01/KEY NOTE 28 AND PD-1.01/ KEY NOTE 4: |
| | RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING: |
| | ***A) A WATER RISER DIAGRAM TO INCLUDE ALL COMPONENTS |
| | AND SIZING OF THE HOT AND COLD WATER PIPING INTEGRATED |
| | WITH EXISTING |
| | ***B) A DETAIL FOR INSTALLATION OF UNITS TO INCLUDE ALL |
| | DOMESTIC WATER PIPING AND GAS PIPING. |
| | ***C) A DETAIL FOR STRUCTURAL SUPPORT SYSTEM. |
| | A PLAN REVISION WILL BE REQUIRED SHOWING THE ABOVE. |
| | REVISION SHALL BE SUBMITTED, APPROVED AND IN PLACE AT |
| | TIME OF INSPECTION. |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO |
| | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED |
| | BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. SO THAT APPROPRIATE |
| | ACTION CAN BE TAKEN BY PLAN REVIEWER, PLEASE ADVISE |
| | (CONTACT SAMANTHA HILL, CHIEF PLANS EXAMINER, |
| | [email protected] OR RYAN BROWN, CHIEF PLUMBING INSPECTOR, |
| | [email protected])WHEN THE APPLICATIONS HAVE BEEN MADE. |
| | PROVIDE THE PERMIT NUMBERS. |
| | A SEPARATE PERMIT IS REQUIRED FOR EACH, HOWEVER A |
| | REVIEW OF THE SYSTEMS UNDER THE MAIN PERMIT IS ALSO |
| | REQUIRED. |
| | NOTE: THE CIVIL DRAWINGS SUBMITTED ON 9/29 (C-1.00, |
| | C-2.00, C-3.00, C-4.00) DO NOT SHOW ANY INDICATION OF A |
| | GREASE INTERCEPTOR |
| | |
| | 2. COMPLIED |
| | |
| | 3. COMPLIED |
| | |
| | 4. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| | PRIOR TO A PLUMBING REVIEW APPROVAL. |
| | PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| | ***B) SECOND REQUEST: A.602/ KEYNOTE 3: PLUMBING |
| | FIXTURE SCHEDULE CALL FOR FLOOR MOUNTED WATER CLOSET. |
| | PER FBC ACC 604.8.1.1., PROVIDE A 60 INCH BY 59 INCH |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSET. RECONCILE WITH |
| | A.601/WATER CLOSET DETAIL. PROVISO: A-602/KEYNOTE 3; |
| | CLEAR FLOOR SPACE FOR WATER CLOSET SHALL BE 60 INCHES |
| | BY 59 INCHES |
| | ***F) SECOND REQUEST: PER FBC ACC 604.8, TOILET PAPER |
| | DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7 |
| | INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | ***J) COMPLIED |
| | ***K) COMPLIED |
| | ***L) SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED |
| | ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH |
| | THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES |
| | (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER |
| | FBC ACC 603.3. |
| | ***M) SECOND REQUEST: PROVIDE ELEVATION DETAIL FOR THE |
| | DRINKING FOUNTAIN SHOWING COMPLIANCE WITH FBC ACC |
| | 602.2, 602.3, 602.4, 602.5 AND 602.7 |
| | NEW COMMENT: THE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | FBC ACC 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 |
| | INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR |
| | SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO |
| | THE CIRCULATION PATH. |
| | |
| | 5.N/A |
| | |
| | 6.P-2.01/KEYNOTE 2, A.101B/KEYNOTE 15 AND |
| | A.101C/KEYNOTE 15, D.101/KEYNOTE 27: ALL NOTE REMOVAL |
| | OF EXISTING PLUMBING FIXTURES AND REPLACE WITH NEW. RMS |
| | 128/129 AND 130/131 ARE RECONFIGURED TO ELIMINATE ONE |
| | BATHROOM IN EACH CONFIGURATION. |
| | PER WPB FBC 107.2.1., PROVIDE THE FOLLOWING: |
| | ***A) SECOND REQUEST: PER FBC ACC 809.4, PLEASE |
| | IDENTIFY THE ACCESSIBLE GUEST ROOMS AND PROVIDE |
| | ELEVATION AND PLAN DETAILS FOR ACCESSIBLE BATHING |
| | ROOM(S) SHOWING COMPLIANCE WITH FBC ACC 603 THROUGH |
| | 610. |
| | ***B) COMPLIED |
| | ***C) COMPLIED |
| | ***D) RMS 128/129 AND 130/131 ARE RECONFIGURED TO |
| | ELIMINATE ONE BATHROOM IN EACH CONFIGURATION. SEE |
| | PROVISO: A PLAN REVISION |
| | WILL BE REQUIRED SHOWING THE REVISED WATER AND |
| | SANITARY. REVISION SHALL BE SUBMITTED, APPROVED AND IN |
| | PLACE AT TIME OF INSPECTION. |
| | |
| | 7. SECOND REQUEST: P-3.01/KITCHEN: ITEMS 1.1, 1.3 AND |
| | 90, EVAPORATOR COIL DRAINS SHALL NOT DISCHARGE TO THE |
| | GREASY WASTE (FBC PL 1003.2), OR TO SANITARY (WPB CODE |
| | OF ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5). |
| | PER WPB FBC 107.2.1, DISCHARGE TO STORM OR TO DRYWELL. |
| | PROVIDE ROUTING AND A DETAIL. |
| | |
| | 8. P-3.01/KITCHEN: ITEMS 84, 85, 88 AND FLOOR DRAINS |
| | NOT RECEIVING GREASY WASTE SHALL NOT DISCHARGE TO THE |
| | GREASY WASTE (FBC PL 1003.2). DISCHARGE TO SANITARY. |
| | NEW COMMENT: ITEM 65 HAND SINK SHALL NOT DISCHARGE TO |
| | THE GREASE (FBC PL 1003.2) |
| | NEW COMMENT: ITEMS 1.1 AND 1.3 EVAPORATOR COILS SHALL |
| | NOT DISCHARGE TO THE GREASY WASTE (FBC PL 1003.2) OR TO |
| | SANITARY (WPB CODE OF ORDINANCE CAPTER (), ARTICLE 3, |
| | SECTION 90-12B5) DISCHARGE TO STORM OR DRYWELL. PROVIDE |
| | ROUTING AND A DETAIL. |
| | |
| | 9. P-3.01/KITCHEN: PER FBC PL 708.1.3, PROVIDE AN |
| | IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS |
| | WELL. |
| | |
| | 10. SECOND REQUEST: P-3.02/BAR: UNDERCOUNTER |
| | REFRIGERATION COIL AND BACK BAR COOLER SHALL NOT |
| | DISCHARGE TO THE GREASY WASTE (FBC PL 1003.2), OR TO |
| | SANITARY (WPB CODE OF ORDINANCE CHAPTER 90, ARTICLE 3, |
| | SECTION 90-12B5). PER WPB FBC 107.2.1, DISCHARGE TO |
| | STORM OR TO DRYWELL. PROVIDE ROUTING AND A DETAIL. |
| | |
| | 11. SECOND REQUEST: P-3.02/BAR: BAR EQUIPMENT SHALL NOT |
| | DISCHARGE TO THE GREASY WASTE (FBC PL 1003.2). |
| | DISCHARGE TO SANITARY. |
| | |
| | 12. SECOND REQUEST: P-3.02/BAR: PER FBC PL 901.2, |
| | 901.2.1 AND 909.1, PROVIDE A VENT(S) FOR THE SYSTEM. |
| | COMPLY WITH ONE OR MORE OF THE METHODS LAID OUT IN FBC |
| | PL CHAPTER 9. TO BE CLEAR, THERE SHALL BE AT LEAST ONE |
| | VENT TO THE OUTSIDE OF THE BUILDING PER FBC PL 904.1 |
| | |
| | 13. SECOND REQUEST: P-3.02/BAR: PER FBC PL 708.1.3, |
| | PROVIDE AN IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 |
| | AS WELL. |
| | |
| | 14.THIS COMMENT IS NOT APPLICABLE: P3.03/GRILL: BAR |
| | EQUIPMENT SHALL NOT DISCHARGE TO THE GREASY WASTE (FBC |
| | PL 1003.2). DISCHARGE TO SANITARY. |
| | NEW COMMENT: P3.03/GRILL- HAND SINK SHALL NOT DISCHARGE |
| | TO THE GREASE (FBC PL 1003.2) |
| | |
| | 15. SECOND REQUEST: P3.03/GRILL: PROVIDE INDIVIDUAL |
| | VENT TO THE OUTDOORS PER FBC PL 904.1. |
| | TO BE CLEAR, THERE SHALL BE AT LEAST ONE VENT TO THE |
| | OUTSIDE OF THE BUILDING PER FBC PL 904.1 |
| | |
| | 16. SECOND REQUEST: P3.03/GRILL: PER FBC PL 708.1.3, |
| | PROVIDE AN IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 |
| | AS WELL. |
| | |
| | 17. COMPLIED |
| | |
| | 18. SECOND REQUEST: P-3.04/WOMEN'S RESTROOM: PER FBC PL |
| | 909.1, PROVIDE A VENT(S) FOR WC-2 WATER CLOSET. |
| | |
| | 19. SECOND REQUEST: P-3.04/MEN'S RESTROOM: PER FBC PL |
| | 909.1, PROVIDE VENT(S) FOR THE UR URINALS. |
| | |
| | 20. SECOND REQUEST: P-3.04/MEN'S RESTROOM: PER FBC PL |
| | 909.1, PROVIDE A VENT FOR THE 3 INCH FLOOR DRAIN. |
| | |
| | 21. P-3.04/COMMON RESTROOMS: PER FBC PL 708.1.3, |
| | PROVIDE AN IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 |
| | AS WELL. |
| | |
| | 22. P-3.05/DRY STORAGE: PER FBC PL 708.1.3, PROVIDE AN |
| | IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS |
| | WELL. |
| | NEW COMMENT: IF PLUMBING IS NO LONGER REQUIRED FOR DRY |
| | STORAGE THEN REMOVE THE PLUMBING PLAN P3.05 OR EDIT IT |
| | TO REFLECT THE FACT. |
| | |
| | 23. COMPLIED |
| | 24. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPING |
| | MATERIAL SPEC FOR SANITARY SOIL, WASTE AND VENT PIPING. |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE PIPING |
| | MATERIAL SPEC FOR WATER DISTRIBUTION. FBC PL 605.4 |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE PIPING |
| | MATERIAL SPEC FOR HOT WATER PIPE INSULATION. FBC EC |
| | C404.4 (A-E) AND TABLE C403.2.10 |
| | |
| | 25. SECOND REQUEST: ALL COMPONENTS IN THE DOMESTIC |
| | WATER SYSTEM SHALL BE LEAD FREE IN ACCORDANCE WITH FBC |
| | PL 605.2 AND 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE |
| | ON PLANS STATING THE SAME. |
| | |
| | 26. COMPLIED |
| | |
| | 27. COMPLIED |
| | |
| | 28. COMPLIED |
| | NEW COMMENT: WATER HEATER DETAIL HAS BEEN REMOVED; |
| | PROVIDE A NEW DETAIL SHOWING THE PIPING ARRANGEMENT FOR |
| | THE SCHEDULED WATER HEATER, EXPANSION TANK, RELIEF |
| | VALVE, LEONARD MEGATRON PNV-100-LF DIGITAL TEMPERATURE |
| | CONTROL STATION WITH MIXING VALVE, RECIRCULATING PUMP |
| | AND ASSOCIATED VALVES/APPURTENANCES. THE CONTROL |
| | STATION CAN BE INDICATED BY A TAGGED SQUARE; REFERENCE |
| | LEONARD SUBMITTAL DATA SHEET S-PNV-100-LF-M JUNE, 2021 |
| | WHICH SHALL BE PART OF YOUR SUBMITTAL FOR DETAIL. SHOW |
| | PIPING IN AND OUT OF THE STATION. INCLUDE TEMPERATURE |
| | OF HOT WATER OUT OF STATION. SUBMIT LEONARD SUBMITTAL |
| | DATA SHEET S-PNV-100-LF-M JUNE, 2021. |
| | |
| | 29. SECOND REQUEST: P-4.01/WATER HEATER SCHEDULE: EEMAX |
| | EMT1.0 AND EEMAX EMT2.5 ARE STORAGE TANK TYPE WATER |
| | HEATERS. PER WPB FBC 107.2.1, PROVIDE A DETAIL OF WATER |
| | HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| | INCLUDING CW, HW, VALVES, THERMAL EXPANSION CONTROL |
| | DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING |
| | TERMINATION) AND WATER HEATER PAN AND DRAIN INCLUDING |
| | TERMINATION IF IN A LOCATION THAT CAN CAUSE WATER |
| | DAMAGE; COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, |
| | 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | PROVIDE TEMPERATURE OF HOT WATER AT OUTLET. |
| | |
| | 30.COMPLIED |
| | |
| | 31. COMPLIED |
| | |
| | 32. P-3.05/DRY STORAGE: PER FBC PL 1002.4.1, PLEASE |
| | PROVIDE A TRAP SEAL PROTECTION DEVICE FOR THE FLOOR |
| | TROUGH. |
| | NEW COMMENT: IF PLUMBING IS NO LONGER REQUIRED FOR DRY |
| | STORAGE THEN REMOVE THE PLUMBING PLAN P3.05 OR EDIT IT |
| | TO REFLECT THE FACT. |
| | |
| | 33. P-3.05/DRY STORAGE: PER WPB FBC 107.2.1, PLEASE |
| | PROVIDE A SCHEDULE AND SPECIFICATION FOR FLOOR DRAINS, |
| | FLOOR SINKS AND TROUGH DRAINS. |
| | NEW COMMENT: IF PLUMBING IS NO LONGER REQUIRED FOR DRY |
| | STORAGE THEN REMOVE THE PLUMBING PLAN P3.05 OR EDIT IT |
| | TO REFLECT THE FACT. |
| | |
| | 34.P-3.05 & P-4.02/DETAIL 4: PER WPB FBC 107.2.1, SHOW |
| | THE INSTALLATION OF THE BACKFLOW PREVENTER(S) AND |
| | BACKFLOW PREVENTER SPECIFICATION. THE BACKFLOW |
| | PREVENTER IN P-3.05 IS NOT IN-LINE. CLARIFY AND |
| | RECONCILE THE DRAWINGS. |
| | NEW COMMENT: IF PLUMBING IS NO LONGER REQUIRED FOR DRY |
| | STORAGE THEN REMOVE THE PLUMBING PLAN P3.05 OR EDIT IT |
| | TO REFLECT THE FACT. IF P-4.02/DETAIL 4 IS NO LONGER |
| | REQUIRED THEN PLEASE REMOVE IT. OTHERWISE, SPECIFY AND |
| | PROVIDE A BACKFLOW PREVENTER ON THE OUTLET TO THE |
| | ICEMAKER. FBC PL 608.1 |
| | |
| | 35.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A SLAB |
| | REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF THE |
| | REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE |
| | TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER), |
| | MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR |
| | DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT |
| | OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER |
| | WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE |
| | SHALL BE ONSITE FOR FINAL INSPECTION. |
| | |
| | 36. SECOND REQUEST: PER WPB FBC 107.2.1, TO SHOW |
| | COMPLIANCE WITH FBC PL 704.1, PROVIDE NOTE STATING |
| | "HORIZONTAL DRAINAGE PIPING LESS THAN 3 INCH DIAMETER |
| | SHALL HAVE A MINIMUM SLOPE OF 1/4 INCH PER FOOT. 3 INCH |
| | TO 6 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF 1/8 |
| | INCH PER FOOT." |
| | |
| | 37. SEE PROVISO #4 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM |
| | WHEN RESUBMITTING. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |