| Plan Review Notes For Permit 22070773 |
| Permit Number |
22070773 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-10-28 15:06:13 | 2ND REVIEW FMC | | | PERMIT: 22070773 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-0.01: PLEASE PROVIDE THE ZONE AIR EFFECTIVE | | | RATE FOR EACH SPACE IN THE OUTDOOR AIR CALCULATIONS. | | | FMC TABLE 403.3.1.1.1.2 | | | | | | 2) PLEASE EXPLAIN THE KITCHEN AIR BALANCE TABULATION, | | | THE DINING ROOM REQUIRES 522 CFM???S OF OUTDOOR AIR IF | | | THE ZONE AIR EFFECTIVE RATE IS 1. IT COULD BE MORE IF | | | THE ZONE AIR EFFECTIVE RATE IS .8. HOW IS 230 CFM???S | | | OF DINING ROOM OUTDOOR AIR BEING TRANSFERRED INTO THE | | | KITCHEN? FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|