| 2022-10-12 12:00:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22070773 320 BELVEDERE RD |
| | |
| | 2ND REVIEW |
| | |
| | PROVISO: PER FBC FG 305.1, THE INSTALLATION MANUALS FOR |
| | ALL GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE |
| | TIME OF INSPECTION. |
| | |
| | NOTE: A RESPONSE LETTER ADDRESSING EACH ITEM WAS NOT |
| | PROVIDED WITH THIS SUBMITTAL. |
| | |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | NEW COMMENTS: |
| | 1.PD-1.01 CALLS FOR REMOVAL OF EXISTING GAS METER |
| | REGULATOR. P-2.01 CALLS FOR NEW 1-14 INCH GAS SUPPLY |
| | FROM CITY AND A NEW METER/REGULATOR TO DELIVER 2 PSI TO |
| | THE FACILITY. P-3.01 B PLAN AND RISER DIAGRAM SHOWS |
| | EXISTING GAS FROM CITY WITH EXISTING METER |
| | METER/REGULATOR SET AT 11 INCHES WATER COLUMN TO |
| | SERVICE THE FACILITY. |
| | PER WPB FBC 107.2.1 AND 107.3.5.1.5, PLEASE CLARIFY AND |
| | RECONCILE DRAWINGS. |
| | |
| | 2. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PLEASE PROVIDE |
| | TABLE FOR SIZING OF 2 PSI PIPING. SPECIFY LONGEST |
| | DEVELOPED LENGTH FOR 2PSI SYSTEM AND FOR EACH SYSTEM |
| | LESS THAN 2 PSI. |
| | |
| | 3. SPECIFY REGULATOR(S) AND SHOW LOCATION(S) AS |
| | REQUIRED FOR SYSTEM(S) LESS THAN 2PSI. |
| | |
| | REVIEW 1 COMMENTS: |
| | |
| | 1. SECOND REQUEST: P-3.01B/GAS RISER DIAGRAM/GAS SIZES |
| | CHART: PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE |
| | DIMENSION OF "ALL" PIPE SEGMENTS BETWEEN THE SERVICE |
| | REGULATOR AND THE NEW SCHEDULED GAS WATER HEATER TO |
| | RECONCILE LONGEST DEVELOPED LENGTH(S) OF SYSTEM(S) AND |
| | TO SHOW COMPLIANCE WITH PIPE SIZING TABLES IN |
| | ACCORDANCE WITH FBC FG 402.4. |
| | |
| | 2. COMPLIED |
| | |
| | 3. SECOND REQUEST: P-3.01B/KEY NOTE 8/GAS SIZES CHART: |
| | KEY NOTE 8 STATES SERVICE REGULATOR IS SET AT 11 INCHES |
| | W.C. PRESSURE WHICH IS COVERED BY FBC FG TABLE |
| | 402.4(4). GAS SIZE CHART REFERS TO FBC FG TABLE |
| | 402.4(2) WHICH HAS A PRESSURE DROP OF 0.5 INCHES W.C. |
| | BUT CALLS OUT A PRESSURE DROP OF 3.0 INCHES OF W.C. |
| | WHICH WOULD BE COVERED BY FBC FG TABLE 402.4(3). PER |
| | WPB FBC 107.2.1, PLEASE CLARIFY. |
| | |
| | 4. SECOND REQUEST: P-3.01B/GAS RISER DIAGRAM/KEY NOTE |
| | 3: THERE APPEARS TO BE AN APPLIANCE REGULATOR AT THE |
| | WATER HEATER BUT THERE IS NO KEY NOTE APPLIED TO IT. |
| | KEY NOTE 3 IS APPLIED TO COOKING LINE EQUIPMENT BUT NOT |
| | THE WATER HEATER. PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| | ADDITIONALLY, PROVIDE SYSTEM PRESSURE DOWNSTREAM OF THE |
| | APPLIANCE REGULATOR(S). |
| | TO BE CLEAR, PLEASE CLEARL INDICATE ALL 2ND STAGE |
| | REGULATORS FOR ALL EQUIPMENT INCLUDING NEW WATER |
| | HEATER, KITCHEN LINE AND RELOCATED EXISTING IWHS |
| | |
| | 5. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A CHART |
| | LISTING ALL NEW EQUIPMENT AND EXISTING IWHS (TO BE |
| | NOTED AS SUCH) GAS FIXTURES AND APPLIANCES (INCLUDE |
| | QUANTITIES) WITH BTU DEMAND REQUIREMENTS FOR EACH. |
| | PROVIDE TOTAL BTU DEMAND (NEW AND EXISTING) ON THE |
| | SYSTEM. |
| | |
| | 6. SECOND REQUESTP-2.01/KEY NOTE 28 AND PD-1.01/ KEY |
| | NOTE 4: RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE |
| | THE FOLLOWING: |
| | ***A) NOTE DISTANCES FROM EXHAUST OUTLET TO NEAREST |
| | VENT OPENINGS INCLUDING WINDOWS AND DOORS. |
| | ***B) PROVIDE RISER DIAGRAM, INCLUDE VALVES, REGULATORS |
| | AND SIZING OF PIPE SEGMENTS. |
| | ***C) NOT REQUIRED |
| | |
| | 7. SECOND REQUEST: P-2.01/KEY NOTE 29: PER WPB FBC |
| | 107.2.1, PROVIDE MATERIAL SPECIFICATION FOR GAS SERVICE |
| | UNDERGROUND CONDUIT INCLUDING METHOD FOR PROTECTION |
| | AGAINST CORROSION; PROVIDE DETAILS FOR CONDUIT |
| | TERMINATION; INCLUDE VENTING DETAILS |
| | |
| | 8. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL AND |
| | VENT DETAIL FOR THE SCHEDULED RHEEM UNIVERSAL G100-200A |
| | WATER HEATER. DETAIL SHALL PROVIDE THROUGH THE |
| | WALL/ROOF DETAIL WITH ANCHORING. ADDITIONALLY, SHOW THE |
| | EXHAUST ROUTING AND TERMINATION ON P-3.01B/PLAN VIEW. |
| | NEW COMMENT: P4.01 WATER HEATER SCHEDULE NOTES STANDARD |
| | POWER VENT. P-4.03 SHOWS OPTION FOR POWER VENT AND |
| | POWER DIRECT VENT. IF THIS IS A POWER DIRECT VENT, |
| | NOTE, PROVIDE INLET/OUTLET SIZES, MAXIMUM LENGTHS AND |
| | PROVIDE DETAILS AS NOTED ABOVE. |
| | |
| | 9. SECOND REQUEST: PER WPB FBC 107.2.1 AND FBC FG |
| | 304.1, PROVIDE CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | WATER HEATER AND PROVISION TO PROVIDE SAID COMBUSTION |
| | AIR. |
| | NEW COMMENT: P4.01 WATER HEATER SCHEDULE NOTES STANDARD |
| | POWER VENT. P-4.03 SHOWS OPTION FOR POWER VENT AND |
| | POWER DIRECT VENT. IF THIS IS A POWER DIRECT VENT, THEN |
| | CALCULATIONS ARE NOT REQUIRED. IF POWER VENT, PROVIDE |
| | CALCULATIONS AND PROVISION TO PROVIDE SAID COMBUSTION |
| | AIR |
| | |
| | 10. SECOND REQUEST: PER WPB FBC 107.2.1 AND FBC FG |
| | 304.1, PROVIDE CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | COOKING LINE EQUIPMENT AND PROVISION TO PROVIDE SAID |
| | COMBUSTION AIR. |
| | |
| | 11. SECOND REQUEST: PER NFPA 96 SECTIONS 10.4 AND 10.5, |
| | AN EMERGENCY HOOD SHUT OFF VALVE SHALL BE INSTALLED FOR |
| | THE COOKING LINE EQUIPMENT BELOW THE CEILING. THE |
| | MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. A UNION SHALL |
| | BE INSTALLED DOWNSTREAM OF THE MANUAL VALVE. PER WPB |
| | FBC 107.2.1, PROVIDE A DETAIL. |
| | |
| | 12. NOT REQUIRED |
| | |
| | 13. SEE PROVISO |
| | |
| | 14. COMPLIED |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM |
| | WHEN RESUBMITTING. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |