Plan Review Notes
Plan Review Notes For Permit 22070773
Permit Number 22070773
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-12 12:00:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070773 320 BELVEDERE RD
  
 2ND REVIEW
  
 PROVISO: PER FBC FG 305.1, THE INSTALLATION MANUALS FOR
 ALL GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE
 TIME OF INSPECTION.
  
 NOTE: A RESPONSE LETTER ADDRESSING EACH ITEM WAS NOT
 PROVIDED WITH THIS SUBMITTAL.
  
  
 GAS COMMENTS: DENIED
  
 NEW COMMENTS:
 1.PD-1.01 CALLS FOR REMOVAL OF EXISTING GAS METER
 REGULATOR. P-2.01 CALLS FOR NEW 1-14 INCH GAS SUPPLY
 FROM CITY AND A NEW METER/REGULATOR TO DELIVER 2 PSI TO
 THE FACILITY. P-3.01 B PLAN AND RISER DIAGRAM SHOWS
 EXISTING GAS FROM CITY WITH EXISTING METER
 METER/REGULATOR SET AT 11 INCHES WATER COLUMN TO
 SERVICE THE FACILITY.
 PER WPB FBC 107.2.1 AND 107.3.5.1.5, PLEASE CLARIFY AND
 RECONCILE DRAWINGS.
  
 2. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PLEASE PROVIDE
 TABLE FOR SIZING OF 2 PSI PIPING. SPECIFY LONGEST
 DEVELOPED LENGTH FOR 2PSI SYSTEM AND FOR EACH SYSTEM
 LESS THAN 2 PSI.
  
 3. SPECIFY REGULATOR(S) AND SHOW LOCATION(S) AS
 REQUIRED FOR SYSTEM(S) LESS THAN 2PSI.
  
 REVIEW 1 COMMENTS:
  
 1. SECOND REQUEST: P-3.01B/GAS RISER DIAGRAM/GAS SIZES
 CHART: PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE
 DIMENSION OF "ALL" PIPE SEGMENTS BETWEEN THE SERVICE
 REGULATOR AND THE NEW SCHEDULED GAS WATER HEATER TO
 RECONCILE LONGEST DEVELOPED LENGTH(S) OF SYSTEM(S) AND
 TO SHOW COMPLIANCE WITH PIPE SIZING TABLES IN
 ACCORDANCE WITH FBC FG 402.4.
  
 2. COMPLIED
  
 3. SECOND REQUEST: P-3.01B/KEY NOTE 8/GAS SIZES CHART:
 KEY NOTE 8 STATES SERVICE REGULATOR IS SET AT 11 INCHES
 W.C. PRESSURE WHICH IS COVERED BY FBC FG TABLE
 402.4(4). GAS SIZE CHART REFERS TO FBC FG TABLE
 402.4(2) WHICH HAS A PRESSURE DROP OF 0.5 INCHES W.C.
 BUT CALLS OUT A PRESSURE DROP OF 3.0 INCHES OF W.C.
 WHICH WOULD BE COVERED BY FBC FG TABLE 402.4(3). PER
 WPB FBC 107.2.1, PLEASE CLARIFY.
  
 4. SECOND REQUEST: P-3.01B/GAS RISER DIAGRAM/KEY NOTE
 3: THERE APPEARS TO BE AN APPLIANCE REGULATOR AT THE
 WATER HEATER BUT THERE IS NO KEY NOTE APPLIED TO IT.
 KEY NOTE 3 IS APPLIED TO COOKING LINE EQUIPMENT BUT NOT
 THE WATER HEATER. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 ADDITIONALLY, PROVIDE SYSTEM PRESSURE DOWNSTREAM OF THE
 APPLIANCE REGULATOR(S).
 TO BE CLEAR, PLEASE CLEARL INDICATE ALL 2ND STAGE
 REGULATORS FOR ALL EQUIPMENT INCLUDING NEW WATER
 HEATER, KITCHEN LINE AND RELOCATED EXISTING IWHS
  
 5. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A CHART
 LISTING ALL NEW EQUIPMENT AND EXISTING IWHS (TO BE
 NOTED AS SUCH) GAS FIXTURES AND APPLIANCES (INCLUDE
 QUANTITIES) WITH BTU DEMAND REQUIREMENTS FOR EACH.
 PROVIDE TOTAL BTU DEMAND (NEW AND EXISTING) ON THE
 SYSTEM.
  
 6. SECOND REQUESTP-2.01/KEY NOTE 28 AND PD-1.01/ KEY
 NOTE 4: RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWING:
 ***A) NOTE DISTANCES FROM EXHAUST OUTLET TO NEAREST
 VENT OPENINGS INCLUDING WINDOWS AND DOORS.
 ***B) PROVIDE RISER DIAGRAM, INCLUDE VALVES, REGULATORS
 AND SIZING OF PIPE SEGMENTS.
 ***C) NOT REQUIRED
  
 7. SECOND REQUEST: P-2.01/KEY NOTE 29: PER WPB FBC
 107.2.1, PROVIDE MATERIAL SPECIFICATION FOR GAS SERVICE
 UNDERGROUND CONDUIT INCLUDING METHOD FOR PROTECTION
 AGAINST CORROSION; PROVIDE DETAILS FOR CONDUIT
 TERMINATION; INCLUDE VENTING DETAILS
  
 8. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL AND
 VENT DETAIL FOR THE SCHEDULED RHEEM UNIVERSAL G100-200A
 WATER HEATER. DETAIL SHALL PROVIDE THROUGH THE
 WALL/ROOF DETAIL WITH ANCHORING. ADDITIONALLY, SHOW THE
 EXHAUST ROUTING AND TERMINATION ON P-3.01B/PLAN VIEW.
 NEW COMMENT: P4.01 WATER HEATER SCHEDULE NOTES STANDARD
 POWER VENT. P-4.03 SHOWS OPTION FOR POWER VENT AND
 POWER DIRECT VENT. IF THIS IS A POWER DIRECT VENT,
 NOTE, PROVIDE INLET/OUTLET SIZES, MAXIMUM LENGTHS AND
 PROVIDE DETAILS AS NOTED ABOVE.
  
 9. SECOND REQUEST: PER WPB FBC 107.2.1 AND FBC FG
 304.1, PROVIDE CALCULATIONS FOR COMBUSTION AIR FOR THE
 WATER HEATER AND PROVISION TO PROVIDE SAID COMBUSTION
 AIR.
 NEW COMMENT: P4.01 WATER HEATER SCHEDULE NOTES STANDARD
 POWER VENT. P-4.03 SHOWS OPTION FOR POWER VENT AND
 POWER DIRECT VENT. IF THIS IS A POWER DIRECT VENT, THEN
 CALCULATIONS ARE NOT REQUIRED. IF POWER VENT, PROVIDE
 CALCULATIONS AND PROVISION TO PROVIDE SAID COMBUSTION
 AIR
  
 10. SECOND REQUEST: PER WPB FBC 107.2.1 AND FBC FG
 304.1, PROVIDE CALCULATIONS FOR COMBUSTION AIR FOR THE
 COOKING LINE EQUIPMENT AND PROVISION TO PROVIDE SAID
 COMBUSTION AIR.
  
 11. SECOND REQUEST: PER NFPA 96 SECTIONS 10.4 AND 10.5,
 AN EMERGENCY HOOD SHUT OFF VALVE SHALL BE INSTALLED FOR
 THE COOKING LINE EQUIPMENT BELOW THE CEILING. THE
 MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. A UNION SHALL
 BE INSTALLED DOWNSTREAM OF THE MANUAL VALVE. PER WPB
 FBC 107.2.1, PROVIDE A DETAIL.
  
 12. NOT REQUIRED
  
 13. SEE PROVISO
  
 14. COMPLIED
  
  
 END OF COMMENTS.
 PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM
 WHEN RESUBMITTING.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  