2022-08-04 16:47:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070773 320 BELVEDERE RD
  
  
 1ST REVIEW
  
 PROVISO: P-4.01/PLUMBING FIXTURE SCHEDULE CALLS FOR
 SELECTION OF FIXTURES BY OWNER/ARCHITECT. A PLAN
 REVISION WILL BE REQUIRED SHOWING THE MANUFACTURER,
 MODEL. REVISION SHALL BE SUBMITTED, APPROVED AND IN
 PLACE AT TIME OF FINAL INSPECTION.
  
 PROVISO: P-2.01/KEYNOTES 20/21: A 3 INCH SANITARY DRAIN
 IS NOTED FOR THE DRY STORAGE ROOM; CONNECTION TO
 EXISTING SANITARY. A PLAN REVISION WILL BE REQUIRED
 SHOWING THE CONNECTION TO EXISTING. REVISION SHALL BE
 SUBMITTED, APPROVED AND IN PLACE AT TIME OF FINAL
 INSPECTION.
  
 PROVISO: RMS 128/129 AND 130/131 ARE RECONFIGURED TO
 ELIMINATE ONE BATHROOM IN EACH CONFIGURATION. A PLAN
 REVISION WILL BE REQUIRED SHOWING THE REVISED WATER AND
 SANITARY. REVISION SHALL BE SUBMITTED, APPROVED AND IN
 PLACE AT TIME OF FINAL INSPECTION.
  
 PLUMBING COMMENTS: DENIED
  
 1. THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO
 BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED
 BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME.
 A SEPARATE PERMIT IS REQUIRED FOR EACH, HOWEVER A
 REVIEW OF THE SYSTEMS UNDER THE MAIN PERMIT IS ALSO
 REQUIRED.
  
 2. GREASE INTERCEPTOR: P-1.00 CALLS FOR A GB-500
 INTERCEPTOR; P-4.04 CALLS FOR A GB-250 INTERCEPTOR.
 ADDITIONALLY P-1.00 REFERS TO P-4.02 AND SHOULD REFER
 TO P-4.04. PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE THE TWO PLANS.
  
 3. GREASE INTERCEPTOR: PROVIDE AN ENLARGED PIPING
 DIAGRAM SHOWING THE LOCATIONS OF CLEANOUTS, SAMPLING
 POINT AND VENTS AS REQUIRED BY THE MANUFACTURER AND FBC
 PL 1003.9. COORDINATE AND RECONCILE WITH P-1.00
  
 4.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ***B) A.602/ KEYNOTE 3: PLUMBING FIXTURE SCHEDULE CALL
 FOR FLOOR MOUNTED WATER CLOSET. PER FBC ACC 604.8.1.1.,
 PROVIDE A 60 INCH BY 59 INCH CLEAR FLOOR SPACE FOR THE
 WATER CLOSET. RECONCILE WITH A.601/WATER CLOSET DETAIL.
 ***F) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***J) A.602; CLEAR FLOOR SPACE FOR URINAL DOES NOT
 MATCH THE ELEVATION. PER WPB FBC 107.2.1, PLEASE
 CLARIFY AND RECONCILE.
 ***K) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***L) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 ***M) PROVIDE ELEVATION DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH FBC ACC 602.2, 602.3,
 602.4, 602.5 AND 602.7
  
 5.MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER(S)
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ***D) KITCHEN EQUIPMENT
  
 6.P-2.01/KEYNOTE 2, A.101B/KEYNOTE 15 AND
 A.101C/KEYNOTE 15, D.101/KEYNOTE 27: ALL NOTE REMOVAL
 OF EXISTING PLUMBING FIXTURES AND REPLACE WITH NEW. RMS
 128/129 AND 130/131 ARE RECONFIGURED TO ELIMINATE ONE
 BATHROOM IN EACH CONFIGURATION.
 PER WPB FBC 107.2.1., PROVIDE THE FOLLOWING:
 ***A) PER FBC ACC 809.4, PLEASE IDENTIFY THE ACCESSIBLE
 GUEST ROOMS AND PROVIDE ELEVATION AND PLAN DETAILS FOR
 ACCESSIBLE BATHING ROOM(S) SHOWING COMPLIANCE WITH FBC
 ACC 603 THROUGH 610.
 ***B) REGARDING THE SHOWERS; WILL THEY BE TILE FLOOR
 WITH LINER OR A MANUFACTURED COMPARTMENT OR BASE?
 IF MANUFACTURED, PROVIDE A MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL. SHOW COMPLIANCE WITH
 FBC PL 421.1. ASME A112.19.2/CSA B45.1 OR CSA
 B45.5/IAPMO Z124.
 IN ALL CASES, PER FBC PL 421.4.1, BATHTUB FLOORS,
 SHOWER FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR.
 IF TILE FLOOR, PROVIDE A CROSS-SECTION SHOWER
 WALL/FLOOR/DRAIN AND THRESHOLD DETAIL
 DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL 421.5.2
 AS FOLLOWS
 LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED
 BACKING
 LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT
 LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAIN
 LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET
 AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT
 BETWEEN THE LINER AND THE OUTLET
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING WITH
 ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR
 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED
 POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED.
 ***C) PROVIDE A SPECIFICATION FOR THE SHOWER CONTROL
 VALVE SHOWING COMPLIANCE WITH FBC PL 412.3. INDIVIDUAL
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1
 ***D) RMS 128/129 AND 130/131 ARE RECONFIGURED TO
 ELIMINATE ONE BATHROOM IN EACH CONFIGURATION. A PLAN
 REVISION WILL BE REQUIRED SHOWING THE REVISED WATER AND
 SANITARY. REVISION SHALL BE SUBMITTED, APPROVED AND IN
 PLACE AT TIME OF FINAL INSPECTION.
  
  
 7.P-3.01/KITCHEN: ITEMS 1.1, 1.3 AND 90, EVAPORATOR
 COIL DRAINS SHALL NOT DISCHARGE TO THE GREASY WASTE
 (FBC PL 1003.2), OR TO SANITARY (WPB CODE OF ORDINANCE
 CHAPTER 90, ARTICLE 3, SECTION 90-12B5). PER WPB FBC
 107.2.1, DISCHARGE TO STORM OR TO DRYWELL. PROVIDE
 ROUTING AND A DETAIL.
  
 8. P-3.01/KITCHEN: ITEMS 84, 85, 88 AND FLOOR DRAINS
 NOT RECEIVING GREASY WASTE SHALL NOT DISCHARGE TO THE
 GREASY WASTE (FBC PL 1003.2). DISCHARGE TO SANITARY.
  
 9. P-3.01/KITCHEN: PER FBC PL 708.1.3, PROVIDE AN
 IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS
 WELL.
  
 10. P-3.02/BAR: UNDERCOUNTER REFRIGERATION COIL AND
 BACK BAR COOLER SHALL NOT DISCHARGE TO THE GREASY WASTE
 (FBC PL 1003.2), OR TO SANITARY (WPB CODE OF ORDINANCE
 CHAPTER 90, ARTICLE 3, SECTION 90-12B5). PER WPB FBC
 107.2.1, DISCHARGE TO STORM OR TO DRYWELL. PROVIDE
 ROUTING AND A DETAIL.
  
 11. P-3.02/BAR: BAR EQUIPMENT SHALL NOT DISCHARGE TO
 THE GREASY WASTE (FBC PL 1003.2). DISCHARGE TO
 SANITARY.
  
 12.P-3.02/BAR: PER FBC PL 901.2, 901.2.1 AND 909.1,
 PROVIDE A VENT(S) FOR THE SYSTEM. COMPLY WITH ONE OR
 MORE OF THE METHODS LAID OUT IN FBC PL CHAPTER 9.
  
 13.P-3.02/BAR: PER FBC PL 708.1.3, PROVIDE AN
 IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS
 WELL.
  
 14. P3.03/GRILL: BAR EQUIPMENT SHALL NOT DISCHARGE TO
 THE GREASY WASTE (FBC PL 1003.2). DISCHARGE TO
 SANITARY.
  
 15. P3.03/GRILL: PROVIDE INDIVIDUAL VENT TO THE
 OUTDOORS PER FBC PL 904.1.
  
 16. P3.03/GRILL: PER FBC PL 708.1.3, PROVIDE AN
 IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS
 WELL.
  
 17. P3.03/GRILL: P-4.02/DETAIL 6 PROVIDES FOR A TRAP
 PRIMER TO FLOOR DRAIN FROM LAVATORY-TRAP. PLAN SHOWS
 WATER SOURCE TRAP PRIMER FOR WHICH THERE IS NO DETAIL.
 PER WPB FBC 107.2.1, CLARIFY.
  
 18.P-3.04/WOMEN'S RESTROOM: PER FBC PL 909.1, PROVIDE A
 VENT(S) FOR THE WC-2 WATER CLOSETS.
  
 19. P-3.04/MEN'S RESTROOM: PER FBC PL 909.1, PROVIDE
 VENT(S) FOR THE UR URINALS.
  
 20. P-3.04/MEN'S RESTROOM: PER FBC PL 909.1, PROVIDE A
 VENT FOR THE 3 INCH FLOOR DRAIN.
  
 21. P-3.04/COMMON RESTROOMS: PER FBC PL 708.1.3,
 PROVIDE AN IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01
 AS WELL.
  
 22.P-3.05/DRY STORAGE: PER FBC PL 708.1.3, PROVIDE AN
 IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS
 WELL.
  
 23. P-3.04/COMMON RESTROOMS: PER FBC PL 607.1, 607.1.1
 AND 607.1.2, SPECIFY AND PROVIDE AT THE LAVATORIES A
 WATER TEMPERATURE LIMITING DEVICES THAT CONFORM TO ASSE
 1070 AND LIMITING THE TEMPERED WATER TO A MAXIMUM OF
 110F.
  
 24.PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC
 FOR SANITARY SOIL, WASTE AND VENT PIPING.
  
 25.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 26. PER WPB FBC 107.2.1, PROVIDE ENERGY EFFICIENCY FOR
 EACH SCHEDULED WATER HEATER WATER HEATER; COMPLY WITH
 FBC EC TABLE C404.2
  
 27. P-4.02/DETAIL 3: PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION AND SIZE FOR EXPANSION TANK ON THE WATER
 HEATER DETAIL.
  
 28. P-4.02/DETAIL 3: SWING CHECK VALVES WHEN INSTALLED
 IN THE VERTICAL POSITION; FLOW SHOWN IS FROM TOP
 DOWNWARD. VALVE IS DEPENDENT ON GRAVITY TO CLOSE AND
 FLOW SHOULD BE FROM THE BOTTOM UPWARD. IF SWING CHECKS
 ARE TO BE USED THEN IN THIS PARTICULAR CASE, INDICATE
 THE PIPING IN A HORIZONTAL POSITION. IF VERTICAL
 INSTALLATION IS REQUIRED WITH FLOW FROM THE TOP
 DOWNWARD, SPECIFY A VALVE SUCH AS A SPRING CHECK
 SPECIFICALLY DESIGNED FOR THAT PURPOSE. ADDITIONALLY,
 PROVIDE A FLOW DIRECTIONAL ARROW AT THE VALVE. WPB FBC
 107.2.1
  
 29. P-4.01/WATER HEATER SCHEDULE: EEMAX EMT1.0 AND
 EEMAX EMT2.5 ARE STORAGE TANK TYPE WATER HEATERS. PER
 WPB FBC 107.2.1, PROVIDE A DETAIL OF WATER HEATER
 SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW,
 HW, VALVES, THERMAL EXPANSION CONTROL DEVICE (INCLUDING
 SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER
 HEATER PAN AND DRAIN INCLUDING TERMINATION IF IN A
 LOCATION THAT CAN CAUSE WATER DAMAGE; COMPLY WITH FBC
 PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6,
 504.7, 504.7.1 AND 504.7.2. PROVIDE TEMPERATURE OF HOT
 WATER AT OUTLET.
  
 30.PER WPB FBC 107.2.1, PROVIDE TRAP PRIMER DETAIL FOR
 FLOOR DRAINS WHERE A LAVATORY OR SINK P-TRAP SUPPLY IS
 NOT AVAILABLE. SEE P-3.01A/WATER ISOMETRIC KEYNOTE 4.
  
 31.P-4.01/SHOCK ABSORBERS CHART: PER WPB FBC 107.2.1
 AND FBC PL 604.9, PROVIDE NOTE STATING WATER HAMMER
 ARRESTORS SHALL BE ASSE 1010 COMPLIANT.
  
 32. P-3.05/DRY STORAGE: PER FBC PL 1002.4.1, PLEASE
 PROVIDE A TRAP SEAL PROTECTION DEVICE FOR THE FLOOR
 TROUGH.
  
 33. P-3.05/DRY STORAGE: PER WPB FBC 107.2.1, PLEASE
 PROVIDE A SCHEDULE AND SPECIFICATION FOR FLOOR DRAINS,
 FLOOR SINKS AND TROUGH DRAINS.
  
 34.P-3.05 & P-4.02/DETAIL 4: PER WPB FBC 107.2.1, SHOW
 THE INSTALLATION OF THE BACKFLOW PREVENTER(S) AND
 BACKFLOW PREVENTER SPECIFICATION. THE BACKFLOW
 PREVENTER IN P-3.05 IS NOT IN-LINE. CLARIFY AND
 RECONCILE THE DRAWINGS.
  
 35.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 36.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 37. P-2.01/KEY NOTE 28 AND PD-1.01/ KEY NOTE 4:
 RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING:
 ***A) A WATER RISER DIAGRAM TO INCLUDE ALL COMPONENTS
 AND SIZING OF THE HOT AND COLD WATER PIPING INTEGRATED
 WITH EXISTING
 ***B) A DETAIL FOR INSTALLATION OF UNITS TO INCLUDE ALL
 DOMESTIC WATER PIPING AND GAS PIPING.
 ***C) A DETAIL FOR STRUCTURAL SUPPORT SYSTEM.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  