Plan Review Notes
Plan Review Notes For Permit 22070773
Permit Number 22070773
Review Stop G
Sequence Number 1
Notes
Date Text
2022-08-09 14:29:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070773 320 BELVEDERE RD
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
 1. P-3.01B/GAS RISER DIAGRAM/GAS SIZES CHART: PER WPB
 FBC 107.2.1, PROVIDE DIMENSION OF ?ALL? PIPE SEGMENTS
 BETWEEN THE SERVICE REGULATOR AND THE NEW SCHEDULED GAS
 WATER HEATER TO RECONCILE WITH NOTED LONGEST DEVELOPED
 LENGTH OF 165 FEET AND TO SHOW COMPLIANCE WITH PIPE
 SIZING TABLES IN ACCORDANCE WITH FBC FG 402.4.
  
 2. P-3.01B/GAS RISER DIAGRAM: PER WPB FBC 107.2.1, NOTE
 THE MATERIAL TYPE OF THE GAS PIPING.
  
 3. P-3.01B/KEY NOTE 8/GAS SIZES CHART: KEY NOTE 8
 STATES SERVICE REGULATOR IS SET AT 11 INCHES W.C.
 PRESSURE WHICH IS COVERED BY FBC FG TABLE 402.4(4). GAS
 SIZE CHART REFERS TO FBC FG TABLE 402.4(2) WHICH HAS A
 PRESSURE DROP OF 0.5 INCHES W.C. BUT CALLS OUT A
 PRESSURE DROP OF 3.0 INCHES OF W.C. WHICH WOULD BE
 COVERED BY FBC FG TABLE 402.4(3). PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
  
 4. P-3.01B/GAS RISER DIAGRAM/KEY NOTE 3: THERE APPEARS
 TO BE AN APPLIANCE REGULATOR AT THE WATER HEATER BUT
 THERE IS NO KEY NOTE APPLIED TO IT. KEY NOTE 3 IS
 APPLIED TO COOKING LINE EQUIPMENT BUT NOT THE WATER
 HEATER. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 ADDITIONALLY, PROVIDE SYSTEM PRESSURE DOWNSTREAM OF THE
 APPLIANCE REGULATOR(S).
  
 5. PER WPB FBC 107.2.1, PROVIDE A CHART LISTING ALL NEW
 AND EXISTING (TO BE NOTED AS SUCH) GAS FIXTURES AND
 APPLIANCES (INCLUDE QUANTITIES) WITH BTU DEMAND
 REQUIREMENTS FOR EACH. PROVIDE TOTAL BTU DEMAND (NEW
 AND EXISTING) ON THE SYSTEM.
  
 6. P-2.01/KEY NOTE 28 AND PD-1.01/ KEY NOTE 4:
 RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING:
 ***A) NOTE DISTANCES FROM EXHAUST OUTLET TO NEAREST
 VENT OPENINGS INCLUDING WINDOWS AND DOORS.
 ***B) PROVIDE RISER DIAGRAM, INCLUDE VALVES, REGULATORS
 AND SIZING OF PIPE SEGMENTS.
 ***C) PROVIDE DETAIL FOR STRUCTURAL SUPPORT SYSTEM.
  
 7. P-2.01/KEY NOTE 29: PER WPB FBC 107.2.1, PROVIDE
 MATERIAL SPECIFICATION FOR GAS SERVICE UNDERGROUND
 CONDUIT INCLUDING METHOD FOR PROTECTION AGAINST
 CORROSION; PROVIDE DETAILS FOR CONDUIT TERMINATION;
 INCLUDE VENTING DETAILS
  
 8. PER WPB FBC 107.2.1, PROVIDE A MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL AND VENT DETAIL FOR
 THE SCHEDULED RHEEM UNIVERSAL G100-200A WATER HEATER.
 DETAIL SHALL PROVIDE THROUGH THE WALL/ROOF DETAIL WITH
 ANCHORING. ADDITIONALLY, SHOW THE EXHAUST ROUTING AND
 TERMINATION ON P-3.01B/PLAN VIEW.
  
 9. PER WPB FBC 107.2.1 AND FBC FG 304.1, PROVIDE
 CALCULATIONS FOR COMBUSTION AIR FOR THE WATER HEATER
 AND PROVISION TO PROVIDE SAID COMBUSTION AIR.
  
 10. PER WPB FBC 107.2.1 AND FBC FG 304.1, PROVIDE
 CALCULATIONS FOR COMBUSTION AIR FOR THE COOKING LINE
 EQUIPMENT AND PROVISION TO PROVIDE SAID COMBUSTION AIR.
  
 11. PER NFPA 96 SECTIONS 10.4 AND 10.5, AN EMERGENCY
 HOOD SHUT OFF VALVE SHALL BE INSTALLED FOR THE COOKING
 LINE EQUIPMENT BELOW THE CEILING. THE MANUAL SHUTOFF
 VALVE SHALL BE UPSTREAM. A UNION SHALL BE INSTALLED
 DOWNSTREAM OF THE MANUAL VALVE. PER WPB FBC 107.2.1,
 PROVIDE A DETAIL.
  
 12. SUBMIT MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC FG 402.2, AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED.
  
 13. PER FBC FG 305.1, THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION.
  
 14. P-3.01B/KEY NOTE 8 STATES EXISTING SERVICE
 REGULATOR IS SET AT 11 INCHES W.C. PRESSURE. P-2.01/KEY
 NOTE 27 STATES SERVICE REGULATOR IS EXISTING AND THAT
 THE CONTRACTOR SHALL VERIFY THAT IT HAS THE CAPACITY TO
 COMPLY WITH THE NEW GAS DEMAND REQUIREMENTS. TO BE
 CLEAR, PLEASE INDICATE THAT THE 11 INCHES OF WATER
 COLUMN SYSTEM WILL COMPLY WITH THE PROJECT GAS DEMAND
 REQUIREMENTS OR PROVIDE A SERVICE REGULATOR THAT WILL
 COMPLY WITH THE PROJECT GAS DEMAND REQUIREMENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS