| 2022-08-09 14:29:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22070773 320 BELVEDERE RD |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1. P-3.01B/GAS RISER DIAGRAM/GAS SIZES CHART: PER WPB |
| | FBC 107.2.1, PROVIDE DIMENSION OF ?ALL? PIPE SEGMENTS |
| | BETWEEN THE SERVICE REGULATOR AND THE NEW SCHEDULED GAS |
| | WATER HEATER TO RECONCILE WITH NOTED LONGEST DEVELOPED |
| | LENGTH OF 165 FEET AND TO SHOW COMPLIANCE WITH PIPE |
| | SIZING TABLES IN ACCORDANCE WITH FBC FG 402.4. |
| | |
| | 2. P-3.01B/GAS RISER DIAGRAM: PER WPB FBC 107.2.1, NOTE |
| | THE MATERIAL TYPE OF THE GAS PIPING. |
| | |
| | 3. P-3.01B/KEY NOTE 8/GAS SIZES CHART: KEY NOTE 8 |
| | STATES SERVICE REGULATOR IS SET AT 11 INCHES W.C. |
| | PRESSURE WHICH IS COVERED BY FBC FG TABLE 402.4(4). GAS |
| | SIZE CHART REFERS TO FBC FG TABLE 402.4(2) WHICH HAS A |
| | PRESSURE DROP OF 0.5 INCHES W.C. BUT CALLS OUT A |
| | PRESSURE DROP OF 3.0 INCHES OF W.C. WHICH WOULD BE |
| | COVERED BY FBC FG TABLE 402.4(3). PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY. |
| | |
| | 4. P-3.01B/GAS RISER DIAGRAM/KEY NOTE 3: THERE APPEARS |
| | TO BE AN APPLIANCE REGULATOR AT THE WATER HEATER BUT |
| | THERE IS NO KEY NOTE APPLIED TO IT. KEY NOTE 3 IS |
| | APPLIED TO COOKING LINE EQUIPMENT BUT NOT THE WATER |
| | HEATER. PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| | ADDITIONALLY, PROVIDE SYSTEM PRESSURE DOWNSTREAM OF THE |
| | APPLIANCE REGULATOR(S). |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE A CHART LISTING ALL NEW |
| | AND EXISTING (TO BE NOTED AS SUCH) GAS FIXTURES AND |
| | APPLIANCES (INCLUDE QUANTITIES) WITH BTU DEMAND |
| | REQUIREMENTS FOR EACH. PROVIDE TOTAL BTU DEMAND (NEW |
| | AND EXISTING) ON THE SYSTEM. |
| | |
| | 6. P-2.01/KEY NOTE 28 AND PD-1.01/ KEY NOTE 4: |
| | RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING: |
| | ***A) NOTE DISTANCES FROM EXHAUST OUTLET TO NEAREST |
| | VENT OPENINGS INCLUDING WINDOWS AND DOORS. |
| | ***B) PROVIDE RISER DIAGRAM, INCLUDE VALVES, REGULATORS |
| | AND SIZING OF PIPE SEGMENTS. |
| | ***C) PROVIDE DETAIL FOR STRUCTURAL SUPPORT SYSTEM. |
| | |
| | 7. P-2.01/KEY NOTE 29: PER WPB FBC 107.2.1, PROVIDE |
| | MATERIAL SPECIFICATION FOR GAS SERVICE UNDERGROUND |
| | CONDUIT INCLUDING METHOD FOR PROTECTION AGAINST |
| | CORROSION; PROVIDE DETAILS FOR CONDUIT TERMINATION; |
| | INCLUDE VENTING DETAILS |
| | |
| | 8. PER WPB FBC 107.2.1, PROVIDE A MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL AND VENT DETAIL FOR |
| | THE SCHEDULED RHEEM UNIVERSAL G100-200A WATER HEATER. |
| | DETAIL SHALL PROVIDE THROUGH THE WALL/ROOF DETAIL WITH |
| | ANCHORING. ADDITIONALLY, SHOW THE EXHAUST ROUTING AND |
| | TERMINATION ON P-3.01B/PLAN VIEW. |
| | |
| | 9. PER WPB FBC 107.2.1 AND FBC FG 304.1, PROVIDE |
| | CALCULATIONS FOR COMBUSTION AIR FOR THE WATER HEATER |
| | AND PROVISION TO PROVIDE SAID COMBUSTION AIR. |
| | |
| | 10. PER WPB FBC 107.2.1 AND FBC FG 304.1, PROVIDE |
| | CALCULATIONS FOR COMBUSTION AIR FOR THE COOKING LINE |
| | EQUIPMENT AND PROVISION TO PROVIDE SAID COMBUSTION AIR. |
| | |
| | 11. PER NFPA 96 SECTIONS 10.4 AND 10.5, AN EMERGENCY |
| | HOOD SHUT OFF VALVE SHALL BE INSTALLED FOR THE COOKING |
| | LINE EQUIPMENT BELOW THE CEILING. THE MANUAL SHUTOFF |
| | VALVE SHALL BE UPSTREAM. A UNION SHALL BE INSTALLED |
| | DOWNSTREAM OF THE MANUAL VALVE. PER WPB FBC 107.2.1, |
| | PROVIDE A DETAIL. |
| | |
| | 12. SUBMIT MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC FG 402.2, AND |
| | 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. |
| | |
| | 13. PER FBC FG 305.1, THE INSTALLATION MANUALS FOR ALL |
| | GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. |
| | |
| | 14. P-3.01B/KEY NOTE 8 STATES EXISTING SERVICE |
| | REGULATOR IS SET AT 11 INCHES W.C. PRESSURE. P-2.01/KEY |
| | NOTE 27 STATES SERVICE REGULATOR IS EXISTING AND THAT |
| | THE CONTRACTOR SHALL VERIFY THAT IT HAS THE CAPACITY TO |
| | COMPLY WITH THE NEW GAS DEMAND REQUIREMENTS. TO BE |
| | CLEAR, PLEASE INDICATE THAT THE 11 INCHES OF WATER |
| | COLUMN SYSTEM WILL COMPLY WITH THE PROJECT GAS DEMAND |
| | REQUIREMENTS OR PROVIDE A SERVICE REGULATOR THAT WILL |
| | COMPLY WITH THE PROJECT GAS DEMAND REQUIREMENTS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |