| 2022-08-17 14:27:52 | HOTEL ADDITION/REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A700 - WALL P4 SHOULD BE SHOWN AS 1HR FIRE |
| | RATED - AS P4 IS THE DESIGNATION SHOWN ON THE FLOOR |
| | PLAN FOR THE 1HR FIRE RATED WALLS. |
| | |
| | 2) WALLS SEPARATING UNITS FROM UNITS AND UNITS FROM |
| | STORAGE ROOM SHOULD BE SHOWN AS 1 HR FIRE RATED FOR NON |
| | SPRINKLERED R1 BUILDINGS - FBC 420.2 - - - 708.3 |
| | |
| | 3) WALLS SEPARATING UNIT FROM PUBLIC SERVICE AREA |
| | (KITCHEN, PUBLIC RESTROOM ETC.) SHOULD BE SHOWN WITH AN |
| | STC RATING - FBC 1207.2 |
| | |
| | 4) SHOW 2ND FLOOR DECK AREA CEILING SYSTEM TO HAVE AN |
| | IIC RATING OF 50 OR HIGHER - FBC 1207.3 |
| | |
| | 5) SHOW THE ROOF OVERFLOW SCUPPER DIMENSION FROM THE |
| | FINISHED ROOF TO THE BOTTOM OF THE SCUPPER - FBC |
| | 1503.4.2.1 OVERFLOW SCUPPERS. |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING |
| | |
| | 6) PLEASE SHOW THE ACCESSIBLE LIFT TO COMPLY WITH ASME |
| | A18.1 FBC A 410.1 |
| | |
| | 7) PLEASE SHOW THE ACCESSIBLE BAR SEATING AREA - SHOW |
| | COUNTER HEIGHT AND KNEE AND TOE CLEARANCES FBC A 226.2 |
| | |
| | 8) PLEASE SHOW THE ACCESSIBLE GRILL SEATING AREA - SHOW |
| | COUNTER HEIGHT AND KNEE AND TOE CLEARANCES FBC A 226.2 |
| | |
| | 9) PLEASE SHOW THE ACCESSIBLE GUEST ROOMS TO COMPLY |
| | WITH FBC A 224.1.1 |
| | |
| | 10) PLEASE PROVIDE THE SOIL REPORT LISTED ON THE |
| | DRAWINGS. |
| | |
| | 11) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE |
| | ROOFING - REVIEWED AND MARKED APPROVED BY THE DESIGNER |
| | OF RECORD - FBC WPB 107.3.4 |
| | |
| | 12) ROOFING SYSTEMS PRODUCT APPROVALS MAY BE DEFERRED |
| | SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE |
| | CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 |
| | |
| | 13) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE PARKING |
| | TO THE ACCESSIBLE ENTRY (SHOW THAT THE ENTRY IS |
| | ACCESSIBLE) FBC A 206.2.1 - - 206.2.5 RESTAURANTS AND |
| | CAFETERIAS. |
| | IN RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE |
| | SHALL BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED |
| | OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 14) FBC 508.4 SEPARATED OCCUPANCIES. - - WALLS |
| | SEPARATING R1 FROM A2 SHOULD BE 2 HR FIRE RATED - FBC |
| | 508.4.4 SEPARATION. |
| | INDIVIDUAL OCCUPANCIES SHALL BE SEPARATED FROM ADJACENT |
| | OCCUPANCIES IN ACCORDANCE WITH TABLE 508.4. |
| | |
| | 15) FBC 508.3NONSEPARATED OCCUPANCIES. - - THE BUILDING |
| | WILL NEED TO BE SPRINKLERED - FBC EXISTING BUILDING |
| | 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT |
| | SEPARATION. |
| | WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| | NEW OCCUPANCY CLASSIFICATION OR WHERE THERE IS A CHANGE |
| | OF OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| | FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| | 9 OF THE FLORIDA BUILDING CODE, BUILDING, AND THAT |
| | PORTION IS NOT SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING WITH FIRE BARRIERS HAVING A FIRE-RESISTANCE |
| | RATING AS REQUIRED IN THE FLORIDA BUILDING CODE, |
| | BUILDING FOR THE SEPARATE OCCUPANCY, THE ENTIRE |
| | BUILDING SHALL COMPLY WITH ALL OF THE REQUIREMENTS OF |
| | CHAPTER 9 APPLIED THROUGHOUT THE BUILDING FOR THE MOST |
| | RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING |
| | AND WITH THE REQUIREMENTS OF THIS CHAPTER. |
| | |
| | |
| | |