2022-08-17 14:27:52HOTEL ADDITION/REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A700 - WALL P4 SHOULD BE SHOWN AS 1HR FIRE
 RATED - AS P4 IS THE DESIGNATION SHOWN ON THE FLOOR
 PLAN FOR THE 1HR FIRE RATED WALLS.
  
 2) WALLS SEPARATING UNITS FROM UNITS AND UNITS FROM
 STORAGE ROOM SHOULD BE SHOWN AS 1 HR FIRE RATED FOR NON
 SPRINKLERED R1 BUILDINGS - FBC 420.2 - - - 708.3
  
 3) WALLS SEPARATING UNIT FROM PUBLIC SERVICE AREA
 (KITCHEN, PUBLIC RESTROOM ETC.) SHOULD BE SHOWN WITH AN
 STC RATING - FBC 1207.2
  
 4) SHOW 2ND FLOOR DECK AREA CEILING SYSTEM TO HAVE AN
 IIC RATING OF 50 OR HIGHER - FBC 1207.3
  
 5) SHOW THE ROOF OVERFLOW SCUPPER DIMENSION FROM THE
 FINISHED ROOF TO THE BOTTOM OF THE SCUPPER - FBC
 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING
  
 6) PLEASE SHOW THE ACCESSIBLE LIFT TO COMPLY WITH ASME
 A18.1 FBC A 410.1
  
 7) PLEASE SHOW THE ACCESSIBLE BAR SEATING AREA - SHOW
 COUNTER HEIGHT AND KNEE AND TOE CLEARANCES FBC A 226.2
  
 8) PLEASE SHOW THE ACCESSIBLE GRILL SEATING AREA - SHOW
 COUNTER HEIGHT AND KNEE AND TOE CLEARANCES FBC A 226.2
  
 9) PLEASE SHOW THE ACCESSIBLE GUEST ROOMS TO COMPLY
 WITH FBC A 224.1.1
  
 10) PLEASE PROVIDE THE SOIL REPORT LISTED ON THE
 DRAWINGS.
  
 11) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE
 ROOFING - REVIEWED AND MARKED APPROVED BY THE DESIGNER
 OF RECORD - FBC WPB 107.3.4
  
 12) ROOFING SYSTEMS PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
 13) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE PARKING
 TO THE ACCESSIBLE ENTRY (SHOW THAT THE ENTRY IS
 ACCESSIBLE) FBC A 206.2.1 - - 206.2.5 RESTAURANTS AND
 CAFETERIAS.
 IN RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE
 SHALL BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 14) FBC 508.4 SEPARATED OCCUPANCIES. - - WALLS
 SEPARATING R1 FROM A2 SHOULD BE 2 HR FIRE RATED - FBC
 508.4.4 SEPARATION.
 INDIVIDUAL OCCUPANCIES SHALL BE SEPARATED FROM ADJACENT
 OCCUPANCIES IN ACCORDANCE WITH TABLE 508.4.
  
 15) FBC 508.3NONSEPARATED OCCUPANCIES. - - THE BUILDING
 WILL NEED TO BE SPRINKLERED - FBC EXISTING BUILDING
 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION OR WHERE THERE IS A CHANGE
 OF OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT
 FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER
 9 OF THE FLORIDA BUILDING CODE, BUILDING, AND THAT
 PORTION IS NOT SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH FIRE BARRIERS HAVING A FIRE-RESISTANCE
 RATING AS REQUIRED IN THE FLORIDA BUILDING CODE,
 BUILDING FOR THE SEPARATE OCCUPANCY, THE ENTIRE
 BUILDING SHALL COMPLY WITH ALL OF THE REQUIREMENTS OF
 CHAPTER 9 APPLIED THROUGHOUT THE BUILDING FOR THE MOST
 RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING
 AND WITH THE REQUIREMENTS OF THIS CHAPTER.
  
  
  