| Plan Review Notes For Permit 22070748 |
| Permit Number |
22070748 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-11-21 11:45:43 | RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | | | | 1. FBC 107 YOU CANNOT CHANGE THE OCCUPANCY WITH AN | | | INTERIOR DEMO PERMIT. SUBMIT AN APPLICATION THAT MORE | | | CLEARLY DESCRIBES THE SCOPE OF WORK, INCLUDE THE | | | ELIMINATION OF HABITABLE UNITS IN THE DESCRIPTION. THIS | | | PERMIT TYPE WILL BE CHANGED TO COMMERCIAL INTERIOR. | | | | | | 2. SEE ZONING COMMENTS - CANNOT HAVE MORE THAN 2 UNITS | | | ON THE PROPERTY - | | | | | | 3. FBC B 708.1, ON THE PLAN SHOW ALL FIRE RATED WALLS. | | | IT APPEARS THAT WORK WAS DONE WITHOUT PERMITS, NOT | | | CLEAR IF THE TENANT SEPARATION WAS MAINTAINED. | | | | | | 4. FBC B CHAPTER 7, PROVIDE A PLAN WHICH SHOWS BUILDING | | | TYPE, SQUARE FOOT AREA, CLEARLY SHOW OCCUPANCIES, FBC | | | CHAPTER 5. NOTE IF THE BUILDING IS SPRINKLERED OR NOT | | | SPRINKLERED. | | | | | | 5. PLEASE PROVIDE THE PERMIT NUMBER FOR THE EXISTING | | | DUPLEX - - WHEN DEVELOPING THE PLAN, NOTE ITEMS WHICH | | | WERE INSTALLED WITHOUT A PERMIT AS SUCH, DO NOT NOTE | | | THEM AS "EXISTING". ONLY ELEMENTS WHICH WERE LEGALLY | | | PERMITTED AND INSPECTED CAN BE CONSIDERED "EXISTING". | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|