| 2022-07-21 12:58:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION WITHIN THE SCOPE OF WORK OF |
| | USING THE OCCUPANCY FOR STORAGE, WHICH IS CHAGING THE |
| | OCCUPANCY FROM RESIDENTIAL TO STORAGE. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PROPOSED |
| | MATERIALS/PRODUCTS/COMMODITIES BEING STORED. |
| | |
| | |
| | 1A) PER NFPA 101 CH 42 STORAGE OCCUPANCIES ILLUMINATION |
| | OF MEANS OF EGRESS AND EMEERGENCY LIGHTING IS REQUIRED |
| | UNLESS IT IS USED ONLY IN DAYLIGHT HOURS WITH |
| | APPLICABLE NATURAL LIGHTING. |
| | |
| | 42.2.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN |
| | ACCORDANCE WITH SEC TION 7.8. |
| | 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT |
| | HOURS, MEANS OF |
| | EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH |
| | WINDOWS ARRANGED TO |
| | PROVIDE THE REQUIRED LEVEL OF ILLUMINATION ON ALL |
| | PORTIONS OF THE MEANS |
| | OF EGRESS DURING SUCH HOURS, WHEN APPROVED BY THE |
| | AUTHORITY HAVING |
| | JURISDICTION |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF COMPLINACE OR |
| | PROVIDE PER THE REQUIREMENT. |
| | |
| | |
| | |
| | 1B) PER NFPA 101 CH 42 STORAGE OCCUPANCIES MARKING OF |
| | THE MEANS OF EGRESS IS REQUIRED. |
| | |
| | 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10 |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS |
| | |
| | PLEASE PROVIDE THE LOCATION OF THE EXIT(S) ON A FLOOR |
| | PLAN AND THAT IT IS CLEARLY IDENTIFIABLE AS THE EXIT. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |