| Notes |
| Date |
Text |
| 2022-08-29 10:37:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. APPLICANT SUBMITTED DESIGN PRESSURE CALCULATIONS | | | WHICH ARE MUCH LOWER THAN THE DESIGN PRESSURES | | | SPECIFIED BY THE ENGINEER. FYI THESE TWO DOCUMENTS HAVE | | | BEEN LOCKED SO THEY WILL NOT BE ISSUED. | | | | | | 2. FBC B 1609, SEE SINGLE HUNG NOA, PAGE 2. +65/-80 IS | | | HIGHLIGHTED AS THE OPTION PROPOSED. ENGINEER SPECIFIES | | | +67/-67. REVISE AND CHECK ALL. | | | | | | |
|