| Date |
Text |
| 2023-04-04 10:44:49 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 4TH REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | THE PREVIOUS COMMENTS HAVE NOT BEEN ADEQUATELY |
| | ADDRESSED. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) PROVISO. TO BE PROVIDED BY THE STAIR MANUFACTURER |
| | AND APPROVED BY THE DESIGNER OF RECORD BEFORE BEING |
| | PROVIDED TO THE BUILDING DEPARTMENT AS A SUBMITTAL. |
| | SUBMIT SHOP DRAWINGS OF THE STAIRS WITH WELD DETAILS. |
| | FBC 2204.1 |
| | |
| | 7) COMPLIED. |
| | |
| | 8) NOT RESOLVED. [ SHOW THE HAND RAIL EXTENSIONS AT THE |
| | TOP PER SECTION 505.10.2 AND AT THE BOTTOM PER SECTION |
| | 505.10.3. SHOW COMPLIANCE WITH FBC ACCESSIBILITY |
| | SECTION 505 FOR REQUIRED HANDRAILS. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| | |
| | 13) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 14) COMPLIED |
| | |
| | 15) SHOW COMPLIANCE WITH FBC 1011.11 WHICH REQUIRES |
| | HANDRAILS ON EACH SIDE OF THE STAIRS. |
| | |
| | 16) SHOW COMPLIANCE WITH FBC 1014.2 WHICH SPECIFIES THE |
| | HEIGHT OF THE HANDRAILS TO BE NOT LESS THAN 34" NOR |
| | MORE THAN 38". |
| | |
| | NOTE: IT APPEARS THAT THERE MAY BE A MISUNDERSTANDING |
| | OF WHAT IS REQUIRED FOR A COMMERCIAL EXIT STAIR. IT |
| | APPEARS THAT ONE SIDE OF THE STAIR IS AGAINST THE WALL |
| | OF A BUILDING. A GUARD (RAIL) IS REQUIRED ON THE OPEN |
| | SIDE OF STAIRS AND LANDINGS AND ARE REQUIRED TO BE NOT |
| | LESS THAN 42" IN HEIGHT FOR THIS PROJECT. SEE FBC 1015. |
| | ALSO HANDRAILS ARE REQUIRED ON EACH SIDE OF THE STAIRS. |
| | FBC1011.11 THE HANDRAIL HEIGHT IS REQUIRED TO BE NOT |
| | LESS THAN 34" NOR MORE THAN 38" PER FBC 1014.2 AND |
| | SHALL HAVE EXTENSIONS PER FBC 1014.6 & FBC |
| | ACCESSIBILITY SECTION 505. FOR COMMERCIAL APPLICATIONS |
| | THE GUARD (RAILS) ARE NOT ALLOWED TO BE USED AS THE |
| | HANDRAILS BECAUSE OF THE DIFFERENT HEIGHT REQUIREMENTS. |
| | IF YOU HAVE ANY QUESTIONS YOU CAN CALL ME AT |
| | 561-805-6714 TO DISCUSS. |
| | |
| | |