| 2023-02-23 10:46:00 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | THE PREVIOUS COMMENTS HAVE NOT BEEN ADEQUATELY |
| | ADDRESSED. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) NOT RESOLVED. [ NEED TO KNOW THE ACTUAL NUMBER OF |
| | OCCUPANTS THAT WILL BE USING THE STAIRS USING FBC |
| | BUILDING 302.1, 1004.1 AND TABLE 1004.5 FOR DETERMINING |
| | OCCUPANT LOADS BASED ON TYPE OF OCCUPANCY AND AREA OF |
| | THE SPACE. ] SPECIFY THE OCCUPANCY TYPE AND THE |
| | OCCUPANT LOAD THAT THE STAIRS WILL BE SERVICING. FBC |
| | 302.1, 1004.1 & 1027.1 |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) PROVISO. TO BE PROVIDED BY THE STAIR MANUFACTURER |
| | AND APPROVED BY THE DESIGNER OF RECORD BEFORE BEING |
| | PROVIDED TO THE BUILDING DEPARTMENT AS A SUBMITTAL. |
| | SUBMIT SHOP DRAWINGS OF THE STAIRS WITH WELD DETAILS. |
| | FBC 2204.1 |
| | |
| | 7) COMPLIED. |
| | |
| | 8) NOT ADDRESSED. [ SHOW THE HAND RAIL EXTENSIONS AT |
| | THE TOP PER SECTION 505.10.2 AND AT THE BOTTOM PER |
| | SECTION 505.10.3L SHOW COMPLIANCE WITH FBC |
| | ACCESSIBILITY SECTION 505 FOR REQUIRED HANDRAILS. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| | |
| | 13) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 14) PROVIDE A LANDING AT THE TOP OF THE STAIRS AS |
| | REQUIRED BY FBC 1011.6. |
| | |
| | 15) SHOW COMPLIANCE WITH FBC 1011.11 WHICH REQUIRES |
| | HANDRAILS ON EACH SIDE OF THE STAIRS. |
| | |
| | 16) SHOW COMPLIANCE WITH FBC 1014.2 WHICH SPECIFIES THE |
| | HEIGHT OF THE HANDRAILS TO BE NOT LESS THAN 34" NOR |
| | MORE THAN 38". |
| | |
| | |