Plan Review Notes
Plan Review Notes For Permit 22070728
Permit Number 22070728
Review Stop M
Sequence Number 2
Notes
Date Text
2022-12-16 10:31:08 
 1) PROVIDE A DETAIL THAT SHOWS THE EXISTING AND NEW
 HVAC DUCTS DO NOT PENETRATE ANY RATED FIRE ASSEMBLIES.
 SHEET M-1 INDICATES THE AHU IS ABOVE THE CEILING WITH A
 RETURN AIR GRILLE. NONE OF THIS CAN BE IN THE RATED
 ASSENBLY. FMC 607.6.2
  
 2) NOTE 5 OF THE RESPONSE LETTER STAES THAT THE BATH
 EXHAUST FANS WERE DUCTLESS, THE MECHANICAL CODE DOES
 NOT AND HAS NEVER ALLOWED THE BATH EXHAUST FAN TO BE
 DUCTLESS. PLEASE SEE FMC 501.3
  
 501.3 EXHAUST DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT APOINT WHERE IT WILL NOT CAUSE A PUBLIC NUISANCE AND
 NOT LESS THAN THE DISTANCES SPECIFIED IN SECTION
 501.3.1. THE AIR SHALL BE DISCHARGED TO A LOCATION FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC, CRAWL SPACE, OR BE DIRECTED ONTO WALKWAYS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  