| Plan Review Notes For Permit 22070728 |
| Permit Number |
22070728 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-12-16 10:31:08 | | | | 1) PROVIDE A DETAIL THAT SHOWS THE EXISTING AND NEW | | | HVAC DUCTS DO NOT PENETRATE ANY RATED FIRE ASSEMBLIES. | | | SHEET M-1 INDICATES THE AHU IS ABOVE THE CEILING WITH A | | | RETURN AIR GRILLE. NONE OF THIS CAN BE IN THE RATED | | | ASSENBLY. FMC 607.6.2 | | | | | | 2) NOTE 5 OF THE RESPONSE LETTER STAES THAT THE BATH | | | EXHAUST FANS WERE DUCTLESS, THE MECHANICAL CODE DOES | | | NOT AND HAS NEVER ALLOWED THE BATH EXHAUST FAN TO BE | | | DUCTLESS. PLEASE SEE FMC 501.3 | | | | | | 501.3 EXHAUST DISCHARGE. THE AIR REMOVED BY EVERY | | | MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS | | | AT APOINT WHERE IT WILL NOT CAUSE A PUBLIC NUISANCE AND | | | NOT LESS THAN THE DISTANCES SPECIFIED IN SECTION | | | 501.3.1. THE AIR SHALL BE DISCHARGED TO A LOCATION FROM | | | WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A | | | VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN | | | ATTIC, CRAWL SPACE, OR BE DIRECTED ONTO WALKWAYS. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|