Plan Review Notes
Plan Review Notes For Permit 22070728
Permit Number 22070728
Review Stop M
Sequence Number 1
Notes
Date Text
2022-09-29 07:21:211ST REVIEW FMC
 PERMIT: 22070728
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL DRAWING SHOWING A DESIGN THAT
 INCLUDES THE FIRE RATED FLOOR CEILING ASSEMBLY REQUIRED
 FOR TENANT SEPARATION. FMC 607.6.2
  
 2) MECHANICAL DRAWINGS APPEAR TO BE A COPY OF THE
 DIGITALLY SIGNED DRAWING. PROVIDE THE ORIGINAL
 DIGITALLY SIGNED DRAWING. FS 471/481
  
  
 [BF] 607.6.2 MEMBRANE PENETRATIONS. DUCTS AND AIR
 TRANSFER OPENINGS CONSTRUCTED OF APPROVED MATERIALS, IN
 ACCORDANCE WITH SECTION 603, THAT PENETRATE THE CEILING
 MEMBRANE OF A FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/
 CEILING ASSEMBLY SHALL BE PROTECTED WITH ONE OF THE
 FOLLOWING:
  
 1. A SHAFT ENCLOSURE IN ACCORDANCE WITH SECTION 713 OF
 THE FLORIDA BUILDING CODE, BUILDING.
 2. A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DUCT PENETRATES THE CEILING OF
 AFIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY.
 3. A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DIFFUSER WITH NO DUCT ATTACHED
 PENETRATES THE CEILING OF A FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  