2022-12-16 10:08:23SHEET M-1 FOR 1ST FLOOR UNIT J62 IS MISSING NOW. M-1
 AND M-2 ARE NOW THE SAME DRAWING FOR THE 2ND FLOOR UNIT
 J64. PROVIDE ALL DRAWINGS RELEVANT TO THE SCOPE OF WORK
 FOR THIS PROJECT. IF THE FIRST FLOOR DUCTWORK IS TO BE
 INSTALLED IN A CHASE BELOW THE RATED CEILING/FLOOR
 ASSEMBLY PROVIDE A DETAIL OF THIS. FBC 107.3.5
  
 NOTE 5 OF THE RESPONSE LETTER STAES THAT THE BATH
 EXHAUST FANS WERE DUCTLESS, THE MECHANICAL CODE DOES
 NOT AND HAS NEVER ALLOWED THE BATH EXHAUST FAN TO BE
 DUCTLESS. PLEASE SEE FMC 501.3
  
 501.3 EXHAUST DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A PUBLIC NUISANCE
 AND NOT LESS THAN THE DISTANCES SPECIFIED IN SECTION
 501.3.1. THE AIR SHALL BE DISCHARGED TO A LOCATION FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC, CRAWL SPACE, OR BE DIRECTED ONTO WALKWAYS.