| 2022-12-16 10:08:23 | SHEET M-1 FOR 1ST FLOOR UNIT J62 IS MISSING NOW. M-1 | | | AND M-2 ARE NOW THE SAME DRAWING FOR THE 2ND FLOOR UNIT | | | J64. PROVIDE ALL DRAWINGS RELEVANT TO THE SCOPE OF WORK | | | FOR THIS PROJECT. IF THE FIRST FLOOR DUCTWORK IS TO BE | | | INSTALLED IN A CHASE BELOW THE RATED CEILING/FLOOR | | | ASSEMBLY PROVIDE A DETAIL OF THIS. FBC 107.3.5 | | | | | | NOTE 5 OF THE RESPONSE LETTER STAES THAT THE BATH | | | EXHAUST FANS WERE DUCTLESS, THE MECHANICAL CODE DOES | | | NOT AND HAS NEVER ALLOWED THE BATH EXHAUST FAN TO BE | | | DUCTLESS. PLEASE SEE FMC 501.3 | | | | | | 501.3 EXHAUST DISCHARGE. THE AIR REMOVED BY EVERY | | | MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS | | | AT A POINT WHERE IT WILL NOT CAUSE A PUBLIC NUISANCE | | | AND NOT LESS THAN THE DISTANCES SPECIFIED IN SECTION | | | 501.3.1. THE AIR SHALL BE DISCHARGED TO A LOCATION FROM | | | WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A | | | VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN | | | ATTIC, CRAWL SPACE, OR BE DIRECTED ONTO WALKWAYS. |
|