Plan Review Notes
Plan Review Notes For Permit 22070701
Permit Number 22070701
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-07-28 12:21:49THIS PLAN WAS REVIEWED AND PASSED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS PERMIT IS APPROVED FOR DEMO PER THE APPLICATION.
  
 THE FOLLOWING COMMENTS NEED TO BE REVIEWED AND APPLIED
 DURING THE DEMO AND TO THE BUILDING PERMIT FOR
 RECONSTRUCTION AT THE APPLICABLE TIME.
  
 1) THERE ARE INDICATIONS OF WALL REMOVAL AND
 RECONSTRUCTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE WALL AREAS
 REQUIRES AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT ON THE DEMO &
 FLOOR PLAN SHEETS AND ENSURE COMPLIANCE.
  
  
  
 1A) THE REMOVAL AND CONSTRUCTION OF NEW SPACES/AREAS
 MAY INVOLVE FIRE ALARM EQUIPMENT/DEVICES AND MAY
 REQUIRE A REVIEW BY A FIRE ALARM CONTRACTOR FOR
 MODIFICATIONS.
  
 THE FIRE ALARM SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE
 DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THE DEMO &
 FLOOR PLAN SHEETS AND ENSURE COMPLIANCE.
  
  
  
 2) THERE ARE INDICATIONS OF CARPET REMOVAL AND
 REINSTALLATION; HOWEVER THERE ARE NO PRODUCT NAMES NOR
 SPECIFICATION SHEETS, INCLUDING THE CARPER, FOR THE
 REPLACEMENT.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
  
 IF THE PROPOSED FLOORING IS PORCELAIN / CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD
 NOT BE REQUIRED.
  
 PLEASE REVIEW, PROVIDE SPEC SHEETS OR INDICATE THE TILE
 TYPE.
  
 LAMINATE/VINYL FLOORING IS NOT TILE AND A SPEC SHEET
 WOULD BE REQUIRED.
  
  
 3) THERE ARE INDICATIONS OF CEILING WORK AND
 REPAINTING.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THE DEMO &
 FLOOR PLAN SHEETS AND ENSURE COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  