| 2023-03-01 06:03:06 | 4TH PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. THIS COMMENT WAS NOT ADDRESSED - THE WATER HEATER |
| | MUST HAVE A MIXING VALVE INSTALLED. THE WATER HEATER |
| | DETAIL DOES NOT SHOW ONE. |
| | 2020 FPC 607.1.1/613.1 - HOT WATER DELIVERY - PER THIS |
| | SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT |
| | SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER |
| | DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE. |
| | THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE |
| | INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1. |
| | THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC |
| | HANDWASHING PROTECTION FOR TEMPERED WATER. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |