| Date |
Text |
| 2022-11-30 16:02:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22070634 4065 N HAVERHILL RD # B1 |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | NEW COMMENT; GENERAL: THE SUBMITTED PLUMBING PLAN |
| | (SINGLE PAGE) IS MIXING EXISTING WITH NEW AND IS VERY |
| | UNCLEAR REGARDING THE MATTER; ADDITIONALLY, IT IS |
| | CRAMMING ALL THE INFORMATION FOR GAS AND PLUMBING ONTO |
| | A SINGLE PAGE. PER WPB FBC 107.2.1, TO PROVIDE CLARITY, |
| | PLEASE PROVIDE A SEPARATE EXISTING/DEMO PLAN, A |
| | SEPARATE PROPOSED PLAN. BR PREPARED TO ADD PAGES AS |
| | APPLICABLE TO PROVIDE ADEQUATE INFORMATION. |
| | |
| | 1. SIGNATURES APPROVED |
| | |
| | 2.THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION 'TBD' (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| | |
| | 3. PARTIALLY COMPLIED: GREASE INTERCEPTOR: A SEPARATE |
| | PERMIT IS REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER |
| | THE MAIN PERMIT IS ALSO REQUIRED. |
| | ***E) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| | 107.2.1, 107.3.4. |
| | NEW COMMENT: CALCULATIONS FOR GREASE INTERCEPTOR SHALL |
| | NOT INCLUDE HAND SINKS. FBC PL 1003.2. IF MOP SINK AND |
| | PREP SINK DISCHARGE TO GREASY WASTE THEN THEY SHALL BE |
| | INCLUDED IN CALCULATIONS. |
| | NEW COMMENT: GREASE TRAP SUBMITTAL DOES NOT INDICATE |
| | THE SIZE OF THE INTERCEPTOR TO BE USED. PLEASE INDICATE |
| | THE MODEL NUMBER/SIZE ON THE SUBMITTAL. THE |
| | INLET/OUTLET PORTS SHALL BE SIZED TO ACCOMMODATE IN |
| | SIZE OF THE INLET AND OUTLET SIZE OF THE PIPING. FBC PL |
| | 704.2 |
| | NEW COMMENT: RISER DIAGRAM SHOWS A 2-WAY CLEANOUT |
| | UPSTREAM AND DOWNSTREAM OF THE INTERCEPTOR BUT THEY |
| | APPEAR TO BE A CROSS TEE IN THE DIAGRAM. PLEASE SHOW A |
| | 2WAY CO TEE WITH A SMOOTH HORIZONTAL BOTTOM. A |
| | DEPRESSED/TRAPPED BOTTOM IS NOT ALLOWED |
| | |
| | 7.SECOND REQUEST: PLAN SHEET S-3: PER FBC ACC 609.4, |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR MEASURED TO THE TOP (NOT THE CENTER) OF |
| | THE GRIPPING SURFACE |
| | REVISED DETAIL ON S-3 SHOWS 32 INCHES MAXIMUM TO |
| | CENTER; NOTES ON S-1 CORRECT THE SITUATION. PLEASE |
| | CORRECT OR ELIMINATE INCORRECT DIMENSIONS ON DETAIL. |
| | |
| | 9. & 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | PLUMBING FLOOR PLAN SHOWING SANITARY AND WATER |
| | DISTRIBUTION. RECONCILE CONFIGURATION WITH THE RISER |
| | DIAGRAMS (I.E., ADDED BATHROOM IS BACK TO BACK ON FLOOR |
| | PLAN, RISER DIAGRAM SHOWS SIDE BY SIDE). ALL |
| | ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED TO WATER |
| | HEATER, RECIRCULATING PUMP, ETC., EXISTING AND NEW |
| | SHALL BE INCLUDED ON PLAN VIEW AND RISER DIAGRAMS. |
| | EXISTING SHALL BE NOTED AS SUCH. INCLUDE SERVICE ENTRY |
| | TO UNIT. SIZE ALL PIPING SEGMENTS. |
| | TO BE CLEAR, PLAN VIEW AND RISER DIAGRAM SHOULD REFLECT |
| | EACH OTHER |
| | ALL FIXTURES AND EQUIPMENT SHOWN ON THE PLANS REQUIRING |
| | CONNECTIONS SHALL BE SHOWN CONNECTED TO THE PIPING |
| | SYSTEMS |
| | NEW COMMENT: PROVIDE VTR FOR GREASY WASTE SYSTEM. FBC |
| | PL 904.1, 904.1.1, 904.1.2 |
| | |
| | 11. SECOND REQUEST: PER FBC PL 608.1, SPECIFY AND |
| | PROVIDE BACKFLOW PREVENTER FOR ICE MACHINES. |
| | TO BE CLEAR; A BFP IS REQUIRED FOR EACH ICE MACHINE. |
| | INDICATE THE SAME ON THE PLANS |
| | |
| | 13. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | INSULATION SPECIFICATION SPEC FOR HOT WATER INSULATION |
| | COMPLY WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10. |
| | THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN |
| | IN TABLE C403.2.10: |
| | ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY |
| | AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER |
| | HEATER. |
| | |
| | |
| | 16.PARTIALLY COMPLIED: EXISTING WATER HEATER: PER WPB |
| | FBC 107.2.1, PROVIDE THE FOLLOWING; |
| | ***B) PROVIDE TEMPERATURE OF HOT WATER TO DISTRIBUTION |
| | ***E) WATER HEATER/RECIRC PUMP DETAIL SCHEDULE & |
| | DETAIL- PROVIDE DETAIL INTEGRATING WATER HEATER AND |
| | RECIRC PUMP; SHOW ALL VALVES AND APPURTENANCES. |
| | ***G) PLEASE CLARIFY MIXING VALVE AT WATER HEATER ON |
| | HOT WATER OUTLET. |
| | TO BE CLEAR, PROVIDE DETAIL FOR MIXING VALVE AND |
| | CONFORM TO ASSE 1017. FBC PL 607.1.1, 613.1 |
| | |
| | 21. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL |
| | FOR STEAM TABLE AND INDIRECT WASTE SHOWING COMPLIANCE |
| | WITH FBC PL 802.1.1. |
| | |
| | 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN |
| | REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD |
| | ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE |
| | SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP. |
| | TO BE CLEAR, PROVIDE DETAIL |
| | NEW COMMENT: DOES THIS DRAIN CONTRIBUTE FAT, OIL OR |
| | GREASE (FOG) TO THE SYSTEM. IF SO, DISCHARGE THE |
| | RECEPTOR TO THE GREASY WASTE AND ADD TO THE |
| | CALCULATIONS FOR THE INTERCEPTOR. IF NOT, DISCHARGE TO |
| | SANITARY |
| | |
| | 23. HOT WATER DISTRIBUTION IS CORRECTLY NOTED TO BE |
| | RECIRCULATING, BUT THERE IS NO LOOP. PER WPB FBC |
| | 107.2.1, CLARIFY. |
| | TO BE CLEAR, SHOW COMPLETED LOOP |
| | NEW COMMENT: HOT WATER IS REQUIRED AT THE #7 MOP SINK |
| | AS WELL AS THE #8 PREP SINK WHICH IS NOT SHOWN IN THE |
| | WATER DISTRIBUTION RISER DIAGRAM. FBC PL 607.1 |
| | |
| | 31. SECOND REQUEST: ICE MAKER(S), HAND SINKS, STEAM |
| | TABLE AND SERVICE SINKS SHALL NOT DISCHARGE TO THE |
| | GREASY WASTE PER FBC PL 1003.2. |
| | TO BE CLEAR, #11 STEAM TABLE, #2 ICE MAKER DRAIN, #4 |
| | ICE MAKER DRAIN SHALL NOT DISCHARGE TO GREASE |
| | INTERCEPTOR. FBC PL 1003.2. IT IS DETERMINED THE #7 MOP |
| | SINK (SERVICE SINK) MAY DISCHARGE TO THE GREASE |
| | INTERCEPTOR. |
| | NEW COMMENT: PROVIDE WASTE, HOT AND COLD WATER FOR #8 |
| | PREP SINK PER FBC PL 301.3, 602.2, 607.1; IS IT A FOOD |
| | PREP SINK? IF SO, COMPLY WITH FBC PL 802.1.1 OR 801.1.7 |
| | AS APPLICABLE. IF THE WASTE CONTRIBUTES FAT, OIL OR |
| | GREASE (FOG) WASTE RECEPTOR SHALL CONNECT TO GREASY |
| | WASTE. IF NOT, CONNECT RECEPTOR TO SANITARY. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |