| 2022-07-26 16:44:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22070634 4065 N HAVERHILL RD # B1 |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1. THERE ARE NO ELECTRONIC SIGNATURES FOR PLUMBING AND |
| | GAS. ENGINEER'S STAMP ON PDF DOES NOT HAVE A SIGNATURE |
| | AND DATE. SEE SIGNATURES. |
| | |
| | 2. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC FG 402.2, AND 301.3. THE INSTALLATION |
| | MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE |
| | ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1. |
| | |
| | 3.PER WPB FBC 107.2.1, PLEASE HIDE ALL STICKY NOTES ON |
| | PDFS AS THEY INTERFERE WITH INTERPRETING THE PLANS. |
| | |
| | 4. PER WPB FBC 107.2.1, PLEASE INDICATE THE TYPE OF GAS |
| | (LP OR NATURAL) |
| | |
| | 5 PER WPB FBC 107.2.1, INCLUDE ON THE RISER DIAGRAM THE |
| | FOLLOWING: |
| | A. THE LOCATION OF SHUTOFFS AND REGULATORS. |
| | B. SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN |
| | REGULATORS |
| | C. INCLUDE ALL PIPE LENGTHS (SEGMENTS), BTU LOADS, AND |
| | DISTANCES TO THE APPLIANCES THAT WERE USED TO CALCULATE |
| | MINIMUM PIPE SIZES USING THE SIZING TABLES FROM THE |
| | 2020 FGC 402 (INCLUDE REFERENCES TO THE TABLE(S) USED) |
| | |
| | 6. PER WPB FBC 107.2.1, LABEL ON THE RISER DIAGRAM ALL |
| | TYPES OF GAS PIPING MATERIALS BEING INSTALLED 2020 FGC |
| | 403 |
| | |
| | 7. PER WPB FBC 107.2.1, PROVIDE SIZE AND MATERIAL FOR |
| | UNDERGROUND SLEEVE; PROVIDE DETAIL(S) FOR |
| | TERMINATIONSINTERIOR AND EXTERIOR |
| | |
| | 8.I PER WPB FBC 107.2.1, INCLUDE CALCULATIONS FOR |
| | COMBUSTION AIR PER 2020 FGC 304 |
| | |
| | 9. PER WPB FBC 107.2.1, PROVIDE A PLAN SHOWING THE |
| | PIPING DISTRIBUTION, UTILITIES METER/REGULATOR, |
| | EMERGENCY SHUT OFF VALVE, MP REGULATORS, LISTED |
| | SHUT-OFF VALVES, EACH APPLIANCE, ITS LOCATION AND |
| | CORRESPONDING BTU LOAD ON THE PLAN. RECONCILE PLAN VIEW |
| | AND RISER DIAGRAM |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE THE DELIVERY PRESSURE |
| | FROM THE UTILITIES METER/REGULATOR |
| | PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED (AS |
| | SEEMS TO BE THE CASE) THE DOWNSTREAM SIDE OF THE MP |
| | REGULATOR IS A SECOND SYSTEM AND SHALL BE CALCULATED |
| | SEPARATLY. |
| | |
| | 11. PER WPB FBC 107.2.1, PROVIDE DISTANCE FROM REG TO |
| | FURTHEST POINT (PER SYSTEM) |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR EMERGENCY |
| | HOOD SHUT DOWN VALVE. THE VALVE SHALL BE BELOW THE |
| | CEILING. UNION TO BE DOWN STREAM OF MANUAL VALVE. SECS. |
| | 10.4, 10.5 OF NFPA 96-17. |
| | |
| | 13. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE |
| | INSTALLATION OF THE MP REGULATOR(S) SHOWING COMPLIANCE |
| | WITH FBC FG 409.4, 410.2(5)(6)(7). |
| | |
| | 14.PER WPB FBC 107.2.1, SUBMIT MANUFACTURERS |
| | SPECIFICATIONS FOR REGULATORS. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |