| 2022-11-07 12:50:00 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLEASE PROVIDE A ACCURATE FLOOR PLAN SHOWING |
| | EXISTING ELECTRICAL CONDITIONS DETAILING EXISTING |
| | RECEPTACLES, SWITCHES, LIGHTING AND ELECTRIC PANELS IN |
| | PROPOSED WORK AREAS. PROVIDE A SEPARATE PROPOSED |
| | ELECTRIC FLOOR PLAN DETAILING ALL NEW , MODIFIED, |
| | RELOCATED OR ADDED LIGHTING, RECEPTACLES, SWITCHES, |
| | CLEARLY SHOW ALL COUNTER SPACES, VANITY, AND APPLIANCE |
| | LOCATIONS. FBC 107.2 |
| | PLEASE COMPLY WITH ALL NEC CODES INCLUDING THE |
| | FOLLOWING |
| | NEC 210.8 GFCI PROTECTION, |
| | NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION, |
| | NEC 210.52 RECEPTACLE SPACING, |
| | NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT |
| | RECEPTACLES, |
| | NEC 250.140 GROUNDING |
| | NEC 210.11 (C)(3) BATHROOM BRANCH CIRCUITS |
| | AND SMOKE/CARBON ALARMS AS PER FBC R 314 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |