| 2022-07-26 08:23:36 | 1ST REVIEW FMC | | | PERMIT: 22070580 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE EXHAUST FAN AT THE SHOWER AREA IN THE MASTER | | | BATH. FRC R303.3 | | | | | | 2) SHOW EXHAUST TERMINATION LOCATIONS FOR THE EXHAUST | | | DUCTS. FRC M1502.3 | | | | | | 3) SHOW THE DRYER EXHAUST, MATERIAL AND EXHAUST | | | TERMINATION LOCATION. FRC M1502.4 | | | | | | 4) PROVIDE DETAILS FOR THE KITCHEN HOOD, IS IT | | | EXHAUSTED TO THE EXTERIOR? PROVIDE THE CFM?S OF THE | | | BLOWER FAN. FRC M1503 | | | | | | 5) PROVIDE THE ANCHORAGE DETAILS FOR THE CONDENSING | | | UNIT. FRC M1307.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|