| Plan Review Notes For Permit 22070570 |
| Permit Number |
22070570 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-11 08:41:40 | ROOFING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | SCOPE: INSTALL HAMPTON RIB ROOFING OVER OPEN FRAMING | | | | | | PROVIDE A ROOF FRAMING PLAN. IDENTIFY THE STEEL FRAMING | | | GUAGE TO BE INSTALLED. | | | | | | 1.PROVIDE THE DESIGN PRESSURES FOR NEW ROOFING PER | | | TABLE R301.2(2) AND FIGURE R301.2(7) COMPONENT AND | | | CLADDING PRESSURE ZONES | | | R301.2.1.1WIND DESIGN REQUIRED. | | | | | | 2.ENHANCED FASTENER SCHEDULE MAY BE REQUIRED PER THE | | | CALCULATED DESIGN PRESSURES. | | | CALCULATIONS SHALL BE PREPARED BY A QUALIFIED DESIGN | | | PROFESSIONAL. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|