Plan Review Notes
Plan Review Notes For Permit 22070551
Permit Number 22070551
Review Stop P
Sequence Number 2
Notes
Date Text
2022-09-14 07:59:571ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22070551
 9/14/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW PLUMBING PLANS SHOW TWO DWELLINGS ON THE
 SAME LOT WHICH WILL REQUIRE WATER USERS TO INSTALL A
 BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF DELIVERY.
 A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL BE
 REQUIRED FOR THE WATER METER PER THE CITY OF WEST PALM
 CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION CONTROL
 PROGRAM.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 2) P1.1: PROVIDE A CLEANOUT AT THE JUNCTION OF THE
 CABANA BUILDING DRAIN AND SEWER JUNCTION- SECS.
 P3005.2.4 & P3005.2.8 (2) FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved