Plan Review Notes
Plan Review Notes For Permit 22070551
Permit Number 22070551
Review Stop E
Sequence Number 2
Notes
Date Text
2022-10-03 16:08:28ELECTRIC REVIEW FAILED
 1) WORK SCOPE IS STILL NOT CLEAR. DEMO/PROPOSED WORK
 PLAN DETAILS NO WORK IN LIVING ROOM AND YET A LIVING
 ROOM AND DINING ROOM LIGHTING PLAN IS SUBMITTED. PHOTOS
 TAKEN FROM CODE VIOLATION CASE APPEARS TO DETAIL NEW
 RECESSED LIGHT FIXTURE HOLE DRILLED WHICH DO NOT APPEAR
 TO BE IN THE KITCHEN. IN ADDITION OTHER PHOTOS APPEAR
 TO DETAIL NEW SWITCH BOXES AND WIRE INSTALLED. PLEASE
 PROVIDE A CLEAR WORK SCOPE DETAILING ALL NEW WIRING
 INCLUDING BUT NOT LIMITED TO, LIGHTS, SWITCHES, OUTLETS
 OR OTHER WIRING. FBC 107.2
 2) THERE DOES NOT APPEAR TO BE ANY SUBMITTED DOCUMENTS
 TO ADDRESS THE VALUE OF THIS PROJECT AS STATED IN
 RESONSE LETTER. FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  