| 2022-10-18 08:47:03 | 3RD PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. THE COFFEE, HOT WATER, OJ, AND TEA APPEAR TO STILL |
| | BE GOING TO GREASE WASTE. I DO NOT BELIEVE THAT THESE |
| | WOULD HAVE FATS, OILS, OR GREASE DISCHARGED INTO THEM. |
| | IF YOU FEEL THEY WILL, YOU CAN EXPLAIN WHY. OTHERWISE, |
| | PLEASE ROUTE THESE TO THE SANITARY AS WELL. |
| | 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| | FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| | WASTE. PLEASE SHOW THAT THE ICE BINS, HAND SINKS, |
| | DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES |
| | THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE |
| | GOING TO THE SANITARY AND NOT TO THE GREASE WASTE. |
| | |
| | 2. DONE |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |