| 2022-09-26 08:07:55 | 2ND REVIEW FMC |
| | PERMIT: 22070537 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS SUBMITTAL HAS GROWN FROM THE FIRST REVIEW |
| | CYCLE. PROVIDE A SCOPE OF WORK INCLUDING ALL THE NEW |
| | ADDITIONAL WORK. CLOUD ALL CHANGES FOR THIS PROJECT. |
| | THERE ARE REVISIONS TO THE MECHANICAL DRAWINGS BUT |
| | THERE IS NO REVISION NUMBER OR DATE ON THE DRAWINGS. |
| | ADD THE REVISION NUMBER AND DATE ON THE MECHANICAL |
| | DRAWINGS. THE ADDITION OF WORK SHOULD INCLUDE A |
| | REVISION FORM FOR THIS PROJECT INCLUDING THE ADDITIONAL |
| | COST. THIS REVIEWER CANNOT COMPLETE THE MECHANICAL |
| | REVIEW UNTIL YOU PROVIDE THIS INFORMATION. IT IS |
| | UNCLEAR BASED ON THE DRAWING IF A NEW FREEZER AND |
| | WALK-IN COOLER ARE BEING INSTALLED UNDER THIS NEW WORK, |
| | IF SO PLEASE ADD A NOTE ON THE MECHANICAL DRAWING |
| | INDICATING THE NEW FREEZER AND WALK-IN COOLER WILL |
| | REQUIRE A SEPARATE PERMIT APPLICATION AND A SEPARATE |
| | PLAN REVIEW. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |