Plan Review Notes
Plan Review Notes For Permit 22070516
Permit Number 22070516
Review Stop P
Sequence Number 2
Notes
Date Text
2022-11-22 16:35:502ND REVIEW PLUMBING- 2020
 22070516
 11/22/22
  
 CODES IN EFFECT.
  
 FPC- FLORIDA PLUMBING CODE 7TH EDITION 2020
 ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES
 ITEMIZED BELOW THE COMMNT.
  
 1) FAILED. SHEET P-103, JUNIOR SPACE 5: PROVIDE
 PLUMBING FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE
 403.1 FBC P. PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED
 AND PROVIDED NUMBER OF FIXTURES FOR THE TENANT SPACE.
 A) SHEETS A-400, P-101, P-103: SHEET P-101 SHOWS THIS
 SPACE TO BE A FUTURE RESTAURANT BUT THE PLUMBING
 FIXTURE CALCULATIONS ON A-400 INDICATE A STORAGE
 OCCUPANCY.
 B) A-400, P-101, & P-103 A SERVICE SINK IS REQUIRED FOR
 THE JUNIOR SPACE 5 PER TABLE 403.1 FBC P. PLEASE
 CORRECT THE PLANS TO SHOW THE FIXTURE LOCATION AND
 PLUMBING PIPING.
  
 2) FAILED ITEMS B, E, F, G, H, J, K BELOW. P103 JUNIOR
 SPACE 5: PROVIDE ENLARGED TOILET ROOM DRAWINGS AND
 DETAILS SHOWING COMPLIANCE WITH THE FBC 2020
 ACCESSIBILITY CODE AS OUTLINED BELOW.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2. (48-INCH CLEAR FLOOR SPACE
 LENGTH DIMENSION NOT PROVIDED).
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
 1) A-102 & A-400: SHEET A-102 SHOWS 3- ADA SINGLE-USER
 TOILET ROOMS AND A-400 SHOWS 2- ADA SINGLE-USER TOILET
 ROOMS. WHICH IS IT? PLEASE IDENTIFY THE TOILET ROOMS AS
 MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P.
  
 2) A-400 DETAIL 5: THE 30X48-INCH CLEAR FLOOR SPACE
 DIAGRAMS DO NOT APPEAR TO BE LOCATED BEYOND THE ARCS OF
 THE IN-SWINGING DOORS- SEC. 603.2.3 EXCEPTION 2.
  
 3) P-105 & P-106: TEMPERED WATER SHALL BE DELIVERED
 FROM THE NEW LAVATORIES IN ACCORDANCE WITH SEC. 419.5
 FBC P. THE SPECS FOR THE CHRONOMITE C- MICRO POINT OF
 USE WATER HEATERS DO NOT INDICATE THE UNITS ARE
 EQUIPPED WITH INTEGRAL HOT WATER TEMPERATURE LIMITING
 CONTROLS. PLEASE INDICATE ASSE 1070 APPROVED MIXING
 VALVES WILL BE INSTALLED- SEC. 607.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  