| Plan Review Notes For Permit 22070505 |
| Permit Number |
22070505 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-11-18 10:29:08 | THE UPDATED DRAWING DOES NOT SHOW THE DUCT SIZES FOR | | | THE NEW STORAGE ROOM. THE OUTDOOR AIR CALCULATIONS | | | SHOULD HAVE BEEN SUBMITTED AS PART OF THE EQUIPMENT | | | SIZING. PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR | | | THE NEW STORAGE ROOM AND SHOW THAT THE EXISTING RTU CAN | | | PROVIDE THIS OUTDOOR AIR. FMC 403.3.1.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|