2022-11-18 10:29:08THE UPDATED DRAWING DOES NOT SHOW THE DUCT SIZES FOR
 THE NEW STORAGE ROOM. THE OUTDOOR AIR CALCULATIONS
 SHOULD HAVE BEEN SUBMITTED AS PART OF THE EQUIPMENT
 SIZING. PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR
 THE NEW STORAGE ROOM AND SHOW THAT THE EXISTING RTU CAN
 PROVIDE THIS OUTDOOR AIR. FMC 403.3.1.1
  