Plan Review Notes
Plan Review Notes For Permit 22070491
Permit Number 22070491
Review Stop G
Sequence Number 1
Notes
Date Text
2022-10-18 11:53:391ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2413.4.1 - YOU'VE LISTED THE LONGEST RUN
 AT 60 FEET. HOWEVER, THE LONGEST RUN IS CALCULATED FROM
 THE SOURCE TO THE MOST REMOTE APPLIANCE AND IN THIS
 CASE WOULD BE = 80 FEET.
  
 2. 2020 FRC G2439.5 (614.6) MAKEUP AIR FOR DRYER.
 PLEASE SHOW THE CALCULATION FOR THE REQUIREMENT OR
 EXCEPTION TO THE NEED FOR MAKE-UP AIR FOR THE DRYER.
  
 3. 2017 WPB AMENDS 107.2.1 - SEEMS TO BE CONFLICTING
 INFORMATION. YOUR DESCRIPTION SAYS "INSTALL 250 GALLON
 LP TANK". HOWEVER, YOU'VE DETAILED NATURAL GAS AND
 SHOWN A METER? IF A TANK IS INSTALLED, INCLUDE ALL
 DETAILS, LOCATION AND TIE DOWNS. IF NOT, UPDATE THE
 PERMIT DESCRIPTION AND OTHER CONFLICTING INFORMATION.
  
 4. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME,
 AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS
 REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER
 1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
 REFERENCED CODES:
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved