| Plan Review Notes For Permit 22070478 |
| Permit Number |
22070478 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-17 08:37:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR IS LOACTED IN AN AE FLOOD ZONE WITH A | | | BFE OF 7-0' NAVD 88. THE CITY OF WEST PALM BEACH HAS A | | | 2-0' FREEBOARD REQUIREMENT IN THEIR FLOOD ORDINANCE. | | | THIS REQUIRES THE GENERATOR AND ANY OTHER EQUIPMENT | | | THAT SERVICES THE DWELLING TO BE AT OR ABOVE AN | | | ELEVATION OF 9-0' NAVD 88. SPECIFY THE ELEVATION OF THE | | | GENERATOR PAD ON THE PLANS. FBC-R322 AND FBC CITY | | | AMENDMENTS107.2.1 | | | | | | 2) SPECIFY THE WINDLOAD DATA FOR THE GENERATOR ON THE | | | GENERATOR PAD AND ANCHORING DETAILS. FBC-R301.1 | | | | | | 3) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. | | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|