| 2022-09-26 09:23:50 | 3RD PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. --THE MIXING VALVE FOR "HOT WATER" DELIVERY MUST BE |
| | PLACED AT THE HOT WATER SOURCE PER MY PREVIOUS COMMENT. |
| | 2020 FPC 613.1 |
| | |
| | -- NOT ADDRESSED -- ALL HOT WATER MUST BE LIMITED BY A |
| | DEVICE "OTHER THAN THE THERMOSTAT ON THE WATER HEATER". |
| | (607.1.1) AND PER 613.1 MUST BE INSTALLED AT THE HOT |
| | WATER SOURCE. YOUR RESPONSE ADDRESSES TEMPERED WATER, |
| | NOT HOT WATER. YOUR DETAIL FOR TEMPERED WATER IS |
| | SUFFICIENT. |
| | 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE |
| | THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE |
| | LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE |
| | A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT |
| | WATER DELIVERY. THIS WOULD BE IN ADDTION TO THE |
| | REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING |
| | 607.1.2/419.5. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |